SALC-212-174
34
(2) 221A~225A Analog output setting 【With option】
Various setting of analog output is performed.
RESET/SHIFT
MAX/MIN
221A
Ao1 output factor
RESET/
SHIFT
MAX/MIN
222A
Ao2 output factor
RESET/
SHIFT
MAX/MIN
223A
Ao3 output factor
224A
Current output
intrinsic sensitivity
225A
Low input cut
RESET/
SHIFT
MAX/MIN
RESET/
SHIFT
MAX/MIN
◆ 221A~223A AO (analog output) 1~3 output factor.
Sets the output factor of each analog outputs.
Selection by + and - , set value is updated
by SET .
Default setting:
AO1 A(V)(3φ3W),A(U)(1φ3W U-W-N),A(1φ2W)
AO2 A(U)(3φ3W),A(W)(1φ3W U-W-N),OFF(1φ2W)
AO3 A(W)(3φ3W),A(N)(1φ3W U-W-N),OFF(1φ2W)
OFF:
Nothing
+
-
+
-
-
+
-
+
1:A(U)
+
-
2:A(V)
+
-
3:A(W)
+
-
4:DA(U)
9:MDA(W)
-
+
8:MDA(V)
7:MDA(U)
6:DA(W)
5:DA(V)
-
+
-
+
At 3φ3W
◆ 224A Current output intrinsic sensitivity,
Output intrinsic sensitivity (% of rated input power
value to an output upper limit value) is set about
each analog output of current.
The setting range can be selected from the following.
Setting range:40.0~120.0% (0.1% step)
Selection by + and - , set value is updated by
SET .
Default setting:100.0% (Current)
◆ 225A Low input cut
It is the function which makes analog output a lower
limit at the case of a minute input (input which
corresponds to 0.5% or less).
A function can be selected from ON (Use) and OFF (No
operation).
Selection by + and - , set value is updated
by SET .
Default setting:OFF (No operation)
Ao1 output factor
Setting No.
New setting
Now setting
Current output
intrinsic sensitivity
New setting
Now setting
Setting No.
Low input cut
New setting
Now setting
Setting No.
Setting factor