SALC-212-174
37
6. Specification
6.1 Specification and intrinsic error.
Input circuit
Input
3-phase 3-wire
Single-phase 3-wire
Single-phase 2-wire
AC5A 50/60Hz
Measurement
item
Measurement range /
Display specification
Intrinsic error (
15
)
Maximum
measurement
Minimum
measurement
Notes
Digital
display
Analog
output
(
16
)
Current
Maximum demand,
Demand, Instant
AC5A~30kA
±0.5%
±0.5%
○
○
U-V-W phase change (
17
)
Apart from a measurement
range, range setting of a
display and an output is
possible.
Item
Specification
Bar graph
display
Bar graph display of the main-monitor factor is done.
A display of a sub monitor factor can also be set.
Operating
method
Current:Effective value computing type.
Demand current:Arithmetic method according with bimetallic type.
Time
interval
setting
Demand current
0 second / 5 seconds / 10 seconds / 20 seconds / 30 seconds / 40 seconds /
50 seconds / 1 minute / 2 minutes / 3 minutes / 4 minutes / 5 minutes /
6 minutes / 7 minutes / 8 minutes / 9 minutes / 10 minutes / 15 minutes /
20 minutes / 25 minutes / 30 minutes (95% time interval)
The factor
in which
display
setting is
possible
Main monitor
Current (Each phase), Demand current (Each phase),
Maximum demand current (Each phase)
Sub monitor
(Left)
Current (Each phase)
Sub monitor
(Center)
Current (Each phase), Demand current (Each phase),
Maximum demand current (Each phase)
Sub monitor
(Right)
Current (Each phase), Demand current (Each phase),
Maximum demand current (Each phase)
Bar graph
Current (Each phase), Demand current (Each phase),
Maximum demand current (Each phase)
Option
Analog output (3 sets). Alarm output. External operation input.
Note (
15
) If this unit directly measures an inverter output of cycle control, SCR phase angle control or PWM
control, an error may increase due to its operation principle.
Note (
16
) Analog output, alarm output and external operation input are options.
Note (
17
) Single-phase 3-wire (U-W-N):U-W-N, Single-phase 3-wire (U-V-N):U-V-N, Single-phase 3-wire
(V-W-N):V-W-N, Single-phase 2-wire:With no phase display.
● Measurement is possible range.
Measurement
factor
Input
Measurement is possible range
Display
Analog output
Current
AC0~5A
120% of meter full scale. (
18
) 120% of output span.
Demand current
200% of meter full scale. (
18
) 120% of output span.
Note (
18
) If the number of display digits is exceeded in spite of the measurable range, it becomes to 9999
(four-digit display) or 999 (three digit display).