SALC-212-174
21
5. Setting
5.1 Function table
This product has each function setting with a front switch.
<Caution> In case the input circuit is not designated at the case of an order, it is shipping in the default
value of 3-phase 3-wire 110V input.
Setting mode 1. Function table
Setting
No.
Function
Functional description
Default setting
Important
setting
Page
111
Display pattern
Sets the display combination
pattern of the digital 4 displays
and bar graph display.
Pattern 1
○
27,28
112
Main monitor
Sets the display factor of
digital main monitor.
3φ3W A(V)
○
27,28
1φ3W A(U)
1φ2W A
113
Sub monitor (Left)
Sets the display factor of digital
sub monitor (left).
3φ3W A(U)
○
27,28
1φ3W A(W)
1φ2W Nothing
114
Sub monitor (Center)
Sets the display factor of digital
sub monitor (center).
Nothing
○
27,28
115
Sub monitor (Right)
Sets the display factor of digital
sub monitor (right).
3φ3W A(W)
○
27,28
1φ3W A(N)
1φ2W Nothing
116
Bar graph
Sets the display factor of bar
graph.
3φ3W A(V)
○
27,28
1φ3W A(U)
1φ2W A
121AL
(
9
)
Alarm factor
Sets the output factor of alarm.
3φ3W
DA (OR detection of
each phase current)
○
29
1φ3W
DA (OR detection of
each phase current)
1φ2W DA
122AL
(
9
)
Alarm reset method
Sets the output action at the case
of an alarm reset.
AUTO
(Automatic reset)
29
123AL
(
9
)
Alarm contact delay
time
Sets the contact delay time of
alarm.
0 second
29
131H
Demand current upper
limit value
Sets the high-alarm value of demand
current.
80% (Full scale=100%)
30
132
Demand current time
interval
Sets time interval of demand
current.
0 second
○
30
141
Backlight action
Sets the ON/OFF of backlight.
AUTO OFF
31
142
(
10
)
Backlight brightness Sets the brightness of backlight. 3(Middle)
31
Note(
9
) A setting item is not displayed in case there is no corresponding option.
Note(
10
) In the case of green backlight, it does not indicate the setting item of brightness.
When changing the input circuit setting, please be sure to perform a setup from an input circuit setting
in the setting mode 3. After changing the other setting, when the input circuit setting is changed the
set value returns to default value (default value of a changed input circuit).
< Caution >