Setting mode 2. Function table
Setting
No.
Function
Functional description
Default setting
Important
setting
Page
211
Current range
Sets the current-measurement range
(primary current).
3φ3W 100.0A
○
33
1φ3W 500.0A
1φ2W 50.00A
212
Current display
intrinsic sensitivity
Sets the full scale of current meter.
3φ3W 100.0A
33
1φ3W 500.0A
1φ2W 50.00A
213
Digit number of
current range
Sets the digit number of current range.
3φ3W 4 digits
33
1φ3W 4 digits
1φ2W 4 digits
221A
(
11
)
AO1 output factor
Sets the output factor of AO1 (analog
output 1).
3φ3W A(V)
○
34
1φ3W A(U)
1φ2W A
222A
(
11
)
AO2 output factor
Sets the output factor of AO2 (analog
output 2).
3φ3W A(U)
○
34
1φ3W A(W)
1φ2W OFF
223A
(
11
)
AO3 output factor
Sets the output factor of AO3 (analog
output 3).
3φ3W A(W)
○
34
1φ3W A(N)
1φ2W OFF
224A
(
11
)
Current output
intrinsic sensitivity
Sets the analog output sensitivity
(% of a rated input power value to
an output upper limit) of current.
100.0%
34
225A
(
11
)
Low input cut
Sets the function which makes a lower
limit the analog output at the case of
a minute input (adequate to 0.5% or
less) in analog output.
OFF (No operation)
34
231
(
11
)
External operation
input function
Sets the function of the external
operation input.
Alarm reset
○
35
241
Current ON/OFF
Sets the ON/OFF of current measurement
display.
ON
35
242
Demand current ON/OFF
Sets the ON/OFF of demand current
measurement display.
ON
35
251
Set value
initialization
Initializes the settings in the setting
mode 1 and the setting mode 2.
(Return to default setting.)
-
35
Setting mode 3. Function table
Setting
No.
Function
Functional description
Default setting
Important
setting
Page
311
Input circuit phase
wire change
Sets the input circuit or phase wire.
3φ3W 3φ3W
○
36
1φ3W 1φ3W(U-W-N)
1φ2W 1φ2W
321
(
11
)
AO1 BIAS adjustment
Sets the BIAS value of AO1 (analog
output 1).
0.0%
36
322
(
11
)
AO1 SPAN adjustment
Sets the SPAN value of AO1 (analog
output 1).
100.0%
36
323
(
11
)
AO2 BIAS adjustment
Sets the BIAS value of AO2 (analog
output 2).
0.0%
36
324
(
11
)
AO2 SPAN adjustment
Sets the SPAN value of AO2 (analog
output 2).
100.0%
36
325
(
11
)
AO3 BIAS adjustment
Sets the BIAS value of AO3 (analog
output 3).
0.0%
36
326
(
11
)
AO3 SPAN adjustment
Sets the SPAN value of AO3 (analog
output 3).
100.0%
36
Note(