Alarm Control Panel Installer Manual
39
RESTART: This option turns off and immediately re-arms the control panel. This function can be
useful to perform PATROL ROUND to disarm one or more areas getting automatic re-arm after
the programmed exit time area.
TIMER OFF: This option is not subject to TRIGGER, DELAY OR FORCED and works only in the
table step from N.C. to N.O. status. When opened, it locks arming operations subject to a TMER
which are programmed for the AREAS to which it is associated. In practice, it functions as a key to
lock/unlock ON/OFF TIMERS active on the AREAS.
IN AND ZONES
1.25
You can set maximum eight IN AND ZONES couples. For each IN AND ZONES, you can combine two
zones and establish the alarm linkage between them.
After entering the Installer Menu, press
and
to scroll up and down until you reach the IN
Step 1
AND ZONES menu. See Figure 1-21.
IN AND ZONES
Figure 1-21
Press
to enter the programming mode.
Step 2
Press
and
to select the IN AND ZONE that you want to configure, and then press
Step 3
.
By pressing
+ 2, you can enter the EDITING mode for changing the description of IN AND
ZONE.
Configure the settings. See Table 1-14.
Step 4
Press
and
to alter the options. Press
to confirm the setting and move to the next
submenu.
Table 1-14 IN AND ZONE programming settings
Submenu
Setting
STATE
ACTIVE: This IN AND ZONE is enabled.
ISOLATE: This In and Zone is programed but not used.
OFF: This IN AND ZONE is disabled.
Summary of Contents for DHI-ARC3008C
Page 1: ...Alarm Control Panel Installer Manual V1 0 1 ZHEJIANG DAHUA VISION TECHNOLOGY CO LTD ...
Page 16: ...Alarm Control Panel Installer Manual 15 Wiring of detectors Figure 1 6 ...
Page 17: ...Alarm Control Panel Installer Manual 16 Keypad connection Figure 1 7 ...
Page 67: ...Alarm Control Panel Installer Manual 66 Vocal message flow Figure 1 36 ...