ENGLISH
16
6.1
SINGLE ELECTROPUMPS: Characteristics and Interpretations.
Ref. FUNCTION
L1, L2, L3
Terminals for connecting the power supply line.
Earth connection cable.
A
1 - 5
Terminals for connecting the remote control. (Ref 10V dc 5mA. )
C
1 - 7
Terminals for connecting the economy function. (Ref 10V dc 5mA. )
Q
11 - 12
Terminals for connecting the remote alarm.
Contact characteristics:
without potential
, NC (normally closed);
≤
30V DC
≤
1A
H
8 - 10
Pressure transducer input 4-20mA.
Regulating knob / LED green (on) / LED yellow-green (stand-by) - see fig. 1-2 -
Wiring diagram for the control of single electropumps (Fig.4)
6.2
SINGLE ELECTROPUMPS: Basic operation.
No further equipment is necessary for the basic operation of the Hydrodriver.
The converter does not have a mains switch, so it is connected to the power mains; it is
always live.
DIGITAL INPUT CONTROLS (SINGLE ELECTROPUMPS):
−
Start-Stop input control (A) :
to switch on the control, remove the jumper
between terminal 1 and 5.
−
Input control for regulating the economy function (C) :
to switch on the control, remove the jumper
between terminal 1 and 7.
PRESSURE REGULATION (SINGLE ELECTROPUMPS):
All the digital inputs (A – C) must be closed.
1. Unscrew the closing cap of the regulating knob.
2. Turn the knob (in a clockwise direction) until the desired pressure is obtained, referring to the data plate
on the cover of the Hydrodriver.
3. On completing regulation, close the cap of the regulating knob again accurately.
Q
H
A
C
Relé (RL1)
(30 V DC, 1.A max)
DIFFERENTIAL TRANSDUCER