By using the red dip switch on the print 
board, you can either choose to control the 
pump manually or remotely. In the manual 
mode you control the speeds by the rotat-
ing button. When the pump is controlled 
remotely, its controlled analogical.  
The dip switch has the following functions: 
ON = Remote Control 
OFF = Manual Steering 
Contact 2 is without function.

 

This installation guide gives basic instructions which are to be observed 
during installation, operation and maintenance of the circulator. It is therefore 
imperative that this manual is read by the responsible operator prior to the 
installation and should always be kept available at the site. 

It is not only the general safety instructions under the ”Safety” section that 
are to be observed but also the specific information provided throughout this 
guide. 

APPLICATION 

The AGEplus SERIES circulators are used in all types of heating systems. 
By use of the advanced internal speed control, the electronic automatic 
adjustment the circulator performance according to system needs. This 
feature gives both great electrical and thermal savings together with reduced 
noise level in the installation. 

CIRCULATOR MEDIUM

 

Clean, non aggressive and non explosive fluids without any solids or fibres. 

Kinematic viscosity: Max. 10mm2/s. Higher viscosity will cause circulator to 
regulate improperly. Capacities shown on the data sheets are measured 
with water v =1mm

2

/s at 20ºC. 

Suitable for water impurity up to 5mg/dm

3

Please note: 

If any liquid other than water is being circulated, we 

recommend that you contact our representative as the circulator 
characteristics may change.

 

SAFETY

 

     - The surface temperature might be hot. 
     - When venting the circulator (Fig. 6), it could result in a slight    
        escape of hot water or steam! 
     - Circulator should be wired according to the existing regulations 
     - The circulator must always be earthed.. 
     - All the wires must be disconnected before any work is     
       carried out on the circulator.

 

Personnel qualification and training 

Personnel responsible for operation, maintenance, inspection and 
installation of the circulator must be adequately qualified. 

The person responsible for the complete installation must ensure that the 
contents of this manual are fully understood by any personnel working on 
the system. 

INSTALLATION 

1.  The circulator should always be installed with the circulator shaft 

horizontal (See Fig. 1). Direction of flow through the circulator casing is 
indicated by an arrow located on the casing. 

2.  If terminal box is to be repositioned by rotating the motor, care must be  

taken to ensure the casing 0-ring is correctly positioned.      

3.  Ensure pipework alignment and adequately supported to both the          

circulator and pipework. Sharp bends should be avoided nearby the 
circulator. 

4.  If the circulator is mounted in vertical pipework, flow should be upwards. 

If flow is downwards, an air-vent must be fitted at the highest point before 
circulator suction. 

5.  Circulator should never be allowed to operate against a closed valve for 

more then a few minutes at the time. 

6.  To avoid accumulation of impurities in the circulator, make sure that it is 

not mounted at the lowest point in a system. 

7.  It is recommended that isolating valves be fitted either side of the 

circulator. 

8.  Before installing a new pump the system should be thoroughly flushed to 

clear any foreign objects that may be in the pipework. 

AGEplus Series  Water temp. max. [C°]  Ambient temp. max. [C°] 

32-120, 40-100, 

40-140 & 50-140 

110 30 

90 40 
90 30 
70 40 

65-120 & 80-120 

Fig. 1  

VENTING 

Before start up of the circulator, fill the system 
and vent the circulator thoroughly. Venting can 
be achieved by loosening the plug positioned 
in centre of nameplate (See Fig. 6). This proc-
ess should be repeated periodically until all air 
within the system has been removed. Venting 
is best done in manual speed 4. 

ELECTRICAL CONNECTION 

Electrical data is shown on the nameplate. 
The circulator needs no external protection but 
must be earthed.How to connect the wires 
can be seen on the terminals of the circulator. 

Technical data  

Electrical data:                          

 

See nameplate

 

Serial no:                                  

 

See nameplate

 

Max. working pressure:            

 

10 bar

 

Min. static head at 80°C:           

 

0,5 bar (65-120 & 80-120 
- 0,8 bar)

 

Min. static head at 95°C

 

1,5 bar

 

Sound pressure level 

 

30-120 up to 40-140:                        Max. 35 dB(A)

 

50-140 up to 80-120:                          

Max. 50 dB(A)

 

According to EN 12639 

 

INSTALLATION AND OPERATING INSTRUCTIONS 

FILE NO: 

10. 823UK 

DATE: 

May. 11, 2011 

SUPERSEDES: New 
DATE: New 

AGEplus SERIES

 

Analogue 0-10 Volt

 

The AGEplus can be controlled infinitely 
variable by analogue signal from 0-10 V.  
0V = Min.speed;  10V = Max. speed 

 

Remote Start-Stop

 

AGEplus pump has a remote start-stop 
function. A cable must be connected to the 
RUN contact. If a cable should be discon-
nected, the pump will shut down and the 
red light will flash rapidly.

 

DUTY CONTROL 

There are two modes for controlling the circulators. 
• Controlled to follow a specific defined differential pressure at different       

flows (auto). 
 

Fig. 2  

L    N

Net

 

Fig. 3  

Fig. 4  

Fig. 5  

Fig. 6  