30
Expert-50 rev.10
Expert-50
compensation adjustment is 30%, the minimum speed will be adjusted to
70% of full speed when the humidity rises 10% above the humidity set
point. In addition to adjusting the minimum speed, the humidity compen-
sation feature also changes the operation of the minimum ventilation
cycle: if the controller is operating in minimum ventilation mode when
the relative humidity exceeds the humidity set point, the minimum
ventilation fans are operated continuously rather than cycled.
This feature also applies when the minimum ventilation speed is acti-
vated. Note that for the compensation to take place, the compensation
feature must be activated by the user.
Set the function to
HUMIDITY COMPENSATION
using the menu
select buttons. The current speed increment is displayed, as well as
the maximum humidity value
Press the Edit key. The speed
increment flashes. Use the arrow
keys to adjust the speed increment
to the desired value.
Relative
Humidity
Relative
Humidity
Set Point
Stage 1
Min. Speed
Compensation begins
0%
100%
Normal
Min.
Speed
Compensation %
10 %
min. vent. comp.
+ 50% at 70% RH