In addition to these alarms, the controller also monitors the temperature
on deactivated temperature probes. This is useful when heating is
reduced in unused parts of the building. A minimum temperature level is
defined by the user below which an alarm is generated (Low Tº Empty
Z).
Other Alarms
High and low static pressures also generate alarms. A user-defined
delay can be used to delay the alarm (see Static Pressure Control). Note
that static pressure alarms can only be detected when tunnel curtains
are at rest. The Expert-32P also detects water spills by monitoring
water consumption levels.
1
Viewing and Acknowledging Alarms
Set the function to
ALARM
using
the menu select buttons. The
first alarm is displayed along with
its status.
Press the Edit key to acknowledge an unacknowledged alarm. The
alarm status flashes on the display.
Use the arrow keys to change the alarm status to “ acknowledged ”.
2
Adjusting Low and High Alarm Temperatures
The low alarm temperature can be adjusted from 40°F to 0.5°F below
the set point. The high alarm temperature can be adjusted from 0.5°F to
40°F above the set point. A change in the set point will change these
values by the same amount.
Set the function to
START/STOP TEMPERATURE
using the menu
select buttons. The start and stop temperatures for Heater 8 are
displayed and the Heater 8 LED on the right flashes.
Use the output select buttons to
select
ALARM
. The corresponding
LED on the right of the front panel
Low: 65.0°F
High: 95.0°F
T° sensor fail
Active