51
Expert-32P rev.11
VENT DOORS
The vent doors' operation is based on the static pressure level in the room.
They respectively open or close when the pressure exceeds the high or low
pressure set points. In addition, different opening and closing set points
can be defined based on the outside temperature.
In minimum ventilation, the vent doors open during a pre-opening delay
before the activation of stage 1 fans. The same delay is used to close the
vent doors when stage 1 fans return to a stop.
The user can also define a stage level above which the vent doors always
remain closed.
Static Pressure Alarm:
Alarms can be set off if the static pressure level exceeds the user-defined
pressure limits. Refer to Alarm chapter to set the pressure limits.
Note that the vent door parameters are only accessible if a static
pressure sensor is enabled. Otherwise, the parameters shown in
this menu are replaced by the air inlet settings.
1
Reading Current Static Pressure
This menu is only accessible if a static pressure sensor is enabled.
Set the function to
STATIC PRESSURE
using the menu select buttons. The
current static pressure is displayed.
Press the down-arrow key. Today's minimum pressure reading is
displayed, along with the time and date.
Press the down-arrow key once again. Today's maximum pressure read-
ing is displayed, along with the time and date.
Keep pressing the down-arrow key to display the minimum and maxi-
mum pressure values for the past six days. Use the up-arrow key to
return to the previous display screens.
Stat. P _ _ _"WC