
Preparation
7
Pre-Installation Check List
___ Water Pressure:
A minimum of 20 psi at a predetermined flow rate is required to backwash the filter properly, with a maximum
of 60 psi to be used. If pressure exceeds 60 psi a pressure reducing valve must be installed ahead of the Iron-Cleer
®
System.
___ Actual Influent Flow Rate:
(Water, available from well pump, service inlet, etc.) The actual pumping rate must exceed
the backwash rate (drain flow) for the model of filter selected at a minimum of 20 psi. See actual backwash rates in the
Specifications section.
___ Electrical Requirements for Filter Control:
A continuous 110 volts is required to cycle the controls and aeration pump.
Make certain the electrical supply is always on and cannot be turned off with another switch. The system and installation must
comply with all state and local laws and regulations.
___ Existing Plumbing:
The condition of the existing plumbing should be free from lime and iron build-up. Piping that is heavily
built-up with lime and/or iron should be replaced.
___ Equipment Location
: See Figure 1.
___ Location of Aeration and Filter Tank:
See Figure 1. These two tanks should be installed after the pressure tank and as
close to each other as practical. If you want to filter outside hosebibs, be sure the filter system is properly sized to handle the
flow rates required for extended periods of time, in addition to the normal household demand.
___ Drain Line:
All drain lines must be a minimum of 1/2” or equal to the size of the drain line connection at the control valve or
larger. Avoid overhead drain lines when possible. If used, overhead drain lines are not to exceed a height of five feet above
the control valve and should be no more than fifty feet in length.
___ Pressure Relief Valve:
A pressure relief valve is installed in aeration tank assembly and it is recommended that a separate
drain line be extended toward the floor or to a drain receptacle.
___ Temperature:
Do not install the unit where it might freeze, or next to a water heater or furnace or in direct sunlight. Outdoor
installation is not recommended and voids the warranty. If installing in an outside location, you must take the steps necessary
to assure the filter, installation plumbing, wiring, etc. are as well protected from the elements (sunlight, rain, wind, heat, cold),
contamination, vandalism, etc. as when installed indoors.
___ Check Valve:
On applications where there is a non-filtered demand for water such as joint wells (where the filter system is
only installed in one of two or more homes), outside hosebibs, farms with outbuildings, yard hydrants, etc. a spring loaded
check valve is provided and must be installed ahead of the aeration tank. See Figure 7, page 12. It is recommended to install
the check valve in a vertical up-flow position.
___ By-Pass Valves:
Two bypass valves are provided with the filter system. One bypass valve is used for the control valve and
the other bypass valve is used for the aeration tank.
___ Filtered Water:
Normally, filtered water is furnished to all household lines; however, outside faucets are typically left on raw
water. If filtered water is provided to outside faucets, the filter system must be sized accordingly.
___ Treated Water:
The filter system should be installed after the pressure tank and before the water softener and water heater.
___ Electrical Facilities:
A ten(10) foot cord and wall mount plug-in transformer are provided with the filter control. A six(6) foot
power cord is provided with the compressor. The customer should provide a receptacle, preferably one not controlled by a
switch that can be turned off accidentally. Observe local electrical codes.
Note:
Most codes require an anti-syphon device or air-gap. Observe all local plumbing codes and drain restrictions. The
system and installation must comply with all state and local laws and regulations.
For installations in massachusetts, the Commonwealth of massachusetts plumbing code 248 CmR shall be adhered
to. Consult with your licensed plumber for installation of this system.
Note:
The filter control valve works on 24v - 60Hz electrical power only. Be sure to use the included transformer. Be sure
the electrical outlet and transformer are in an inside location to protect from moisture. Properly ground to conform with all
governing codes and ordinances.