68
VIII. Electrical
(continued)
Figure 46: Multiple Boiler W
iring Diagram w/T
ekmar 264 Control
Tekmar 264 Based Control System (or equal)
Sequence of Operation
The
Tekmar 264 Control (or equal) can control up to four (4) boilers and an Indirect W
ater Heater by utilizing stage firing. When a call for heat is received by the
Tekmar 264
Control, the control will fire either one or more boilers in sequential firing mode to establish a required reset water temperature in the system supply main based on outdoor temperature.
The boilers will modulate on their own based on each boiler
’s control and will target a setpoint temperature to supply enough input to the system main to satisfy
the desired reset water temperature in the main established by the
Tekmar 264 Control. When a call for Indirect Hot W
ater is generated to the
Tekmar 264, the control will de-
energize the zone pump control (ZC terminal), energize the Indirect pump and sequentially fire the boilers to establish a setpoint temperature in the main for the Indirect Heater using Priority
.
The
Tekmar 264 Control will disable the stage firing and post purge the Indirect Pump to reduce the temperature in the Supply Main near the end of the Indirect
Mode to a point where it will need to be when it changes back to Space Heating Mode.
The
Tekmar 264 Control also has the ability to rotate the lead-lag firing of the boilers to
establish equal operating time for each boiler stage.
Summary of Contents for Phantom X series
Page 14: ...14 III Pre Installation and Boiler Mounting G General continued Figure 5 Boiler Stacking...
Page 47: ...47 VI Water Piping and Trim continued Figure 28 Near Boiler Piping Heating Only...
Page 71: ...71 IX System Start up continued Figure 47 Operating Instructions...
Page 122: ...122 XIII Repair Parts continued...
Page 126: ...126 XIII Repair Parts continued...
Page 129: ...129 XIII Repair Parts continued 10A 10B 10C 10D 10G...
Page 134: ...134...
Page 135: ...135...