6
I. Product Description, Specifications and Dimensional Data
Phantom X Series boilers are condensing high efficiency
gas-fired direct vent hot water boilers designed for use
in forced hot water space or space heating with indirect
domestic hot water heating systems, where supply water
temperature does not exceed 210°F. These boilers have
special coil type stainless steel heat exchangers, constructed,
tested and stamped per Section IV ‘Heating Boilers’ of
ASME Boiler and Pressure Vessel Code, which provide a
maximum heat transfer and simultaneous protection against
flue gas product corrosion. These boilers are not designed
for use in gravity hot water space heating systems or
systems containing significant amount of dissolved oxygen
(swimming pool water heating, direct domestic hot water
heating, etc.).
This manual is for use with boilers having a part number
ending in “C” (example: PHNTM399CHNL2HUC).
Table 2: Dimensions (See Figures 1 and 2)
Table 1: Specifications
Specification
Boiler Model
PHNTM399C
PHNTM500C
Altitude (ft. above sea level)
1
0-10,100
0-10,100
2
Fuel
Shipped for Natural Gas, Field
Converted for LP Gas
Max. Allowable Water Temperature (°F)
210
210
Max. Allowable Working Pressure (psi)
160
160
Factory Supplied Safety Relief Valve (psi)*
50
50
Boiler Water Volume (gal.)
3.4
4.3
Heat Transfer Area (sq. ft.)
41.8
58.1
Approx. Shipping Weight (lb.)
316
368
1
Follow Instructions for High Altitude Installations above 2000 ft. (see Appendix A)
2
PHNTM500C LP cannot be installed above 6,000 ft.
Dimension
Boiler Model
PHNTM399C
PHNTM500C
A - Inch
(mm)
31-3/16
(792)
46-1/2
(1181)
B - Inch
(mm)
5-1/2
(140)
N/A
C - Inch
(mm)
12-3/8
(314)
21-5/16
(541)
D - Inch
(mm)
23
(584)
34-13/16
(884)
E - Inch
(mm)
15-1/8
(384)
28-5/16
(719)
Gas Inlet G - Inch
3/4 (FPT)
Return H - Inch
1-1/2 FPT
2 MPT
Supply J - Inch
1-1/2 FPT
2 MPT
PP Condensate Drain K - Inch
3/4 PVC Compression Coupling
PVC Combustion Air Connector - Inch
4
CPVC/PP/SS Vent Connector - Inch
(mm)
4
(100)
Summary of Contents for Phantom X series
Page 14: ...14 III Pre Installation and Boiler Mounting G General continued Figure 5 Boiler Stacking...
Page 47: ...47 VI Water Piping and Trim continued Figure 28 Near Boiler Piping Heating Only...
Page 71: ...71 IX System Start up continued Figure 47 Operating Instructions...
Page 122: ...122 XIII Repair Parts continued...
Page 126: ...126 XIII Repair Parts continued...
Page 129: ...129 XIII Repair Parts continued 10A 10B 10C 10D 10G...
Page 134: ...134...
Page 135: ...135...