D. Stainless Steel Venting
WARNING
Asphyxiation Hazard. Follow these instructions
and the installation instructions included by
the original stainless steel venting component
manufacturers, Heat Fab, M&G/DuraVent or
Z-Flex, whichever applicable. Failure to do so
could cause products of combustion to enter the
building, resulting in severe property damage,
personal injury or death. Where a conflict arises
between Heat Fab, M&G/DuraVent or Z-Flex
instructions and these instructions, the more
restrictive instructions shall govern.
Do not mix vent components from listed
manufacturers.
Examine all components for possible
shipping damage prior to installation.
All condensate that forms in the vent must be
able to drain back to the boiler.
1. Components
a. Acceptable listed stainless steel vent system
manufacturers and components are shown in
Tables 19, 20 and 21.
b. Alternate listed stainless steel vent system
manufacturers and components are shown in
Tables 20 and 21.
IV. Venting
D. Stainless Steel Venting (continued)
c. Where the use of “silicone” is called for in the
following instructions, use GE RTV 106 or
equivalent for the vent collar. Seal galvanized
combustion air piping sections with any general-
purpose silicone sealant such as GE RTV102.
Seal PVC combustion air piping sections with
PVC cement.
d. Do not drill holes in vent pipe.
2. Field Installation of Stainless Steel Vent
Adapter
(see Figure 22)
a. No adapter is required for stainless steel vent
pipe unless vent diameter is reduced per Table 8.
See Table 19, 20, or 21 for adapters for reduced
vent diameter.
Boiler Model
Nominal Pipe
Diameter
Boiler Adapter
Sidewall * or Roof Termination:
Straight Termination w/Screen
Wall Thimble
PHNTM399C (reduced dia.)
PHNTM500C (reduced dia.)
3 in. (80 mm)
FS0403TR
FSBS3
FSWT3
PHNTM399C (standard dia.)
PHNTM500C (standard dia.)
4 in. (100 mm)
PHNTM399C &
PHNTM500C:
No Adapter Required
FSBS4
FSWT4
Note:
When using room air for combustion, use tee for sidewall vent termination. Termination tee part numbers: FSTT3 (3 in.),
FSTT4 (4 in.).
See M&G DuraVent FasNSeal literature for other required component part numbers such as straight pipe, elbows, firestops, and vent supports.
Table 20: M&G DuraVent FasNSeal Stainless Steel Vent System Components, Single Wall
NOTICE
Do not exceed maximum vent/combustion
air system length. Refer to “2. Vent/
Combustion Air Piping” under “A. General
Guidelines” in this section for maximum
vent/combustion air system length.
Use only vent and combustion air terminals
and terminal locations shown in “3. Vent/
Combustion Air Terminals” under “A.
General Guidelines” of this section.
Summary of Contents for Phantom X series
Page 14: ...14 III Pre Installation and Boiler Mounting G General continued Figure 5 Boiler Stacking...
Page 47: ...47 VI Water Piping and Trim continued Figure 28 Near Boiler Piping Heating Only...
Page 71: ...71 IX System Start up continued Figure 47 Operating Instructions...
Page 122: ...122 XIII Repair Parts continued...
Page 126: ...126 XIII Repair Parts continued...
Page 129: ...129 XIII Repair Parts continued 10A 10B 10C 10D 10G...
Page 134: ...134...
Page 135: ...135...