112
Follow manufacturer application procedure
for proper heating system/boiler cleaning and
preventive treatment.
Above referenced products are available from
Alent plc, Consumer Products Division, 4100
6th Avenue, Altoona, PA 16602, Tel: (972)
547-6002 and/or selected HVAC distributors.
Contact Crown Boiler Co. for specific details.
iii.
Equivalent system water treatment products
may be used in lieu of products referenced
above.
2. System Freeze Protection:
a. The following heating system freeze protection
products are recommended for Phantom X boilers:
i.
Fernox™ Protector Alphi 11 (combined
antifreeze and inhibitor).
Follow manufacturer application procedure
to insure proper antifreeze concentration and
inhibitor level.
Above referenced product is available from
Alent plc, Consumer Products Division, 4100
6th Avenue, Altoona, PA 16602, Tel: (972)
547-6002 and/or selected HVAC distributors.
Contact Crown Boiler Co. for specific details.
b. Equivalent system freeze protection products
may be used in lieu of product referenced above.
In general, freeze protection for new or existing
systems must use specially formulated glycol,
which contains inhibitors, preventing the glycol
from attacking the metallic system components.
Insure that system fluid contains proper glycol
concentration and inhibitor level. The system should
be tested at least once a year and as recommended by
the manufacturer of the glycol solution. Allowance
should be made for expansion of the glycol solution.
WARNING
Poison Hazard. Use only inhibited propylene
glycol solutions specifically formulated for
hydronic systems. Do not use ethylene glycol,
which is toxic and can attack gaskets and seals
used in hydronic systems. Use of ethylene
glycol could result in property damage, personal
injury or death.
E. Condensate Overflow Switch and Condensate
Trap Removal and Replacement:
For removal or replacement of the condensate overflow
switch and/or condensate trap follow the steps below. For
parts identification, refer to Section XIII “Repair Parts”.
1. Condensate Overflow Switch Removal and
Replacement:
a. Disconnect power supply to boiler.
b. Remove 2 wire nuts and disconnect overflow switch
wire pigtails from boiler wiring.
c. Using pliers, release spring clip securing the
overflow switch to condensate trap body and remove
the switch. Note that the switch has factory applied
silicon adhesive seal, which may have to be carefully
cut all around to facilitate the switch removal.
d. Insure the trap overflow switch port is not obstructed
with silicon seal debris, clean as needed.
e. Apply silicon sealant to the replacement switch
threads and install the switch into the trap body
making sure it is properly oriented - the arrow
molded into the switch hex end side must face
down for proper switch operation. See Figure 60
“Condensate Overflow Switch Orientation” for
details.
f. Reconnect the switch wire pigtails to the boiler
wiring and secure with wire nuts.
XI. Service and Maintenance
(continued)
Figure 60: Condensate Overflow Switch Orientation
Summary of Contents for Phantom X series
Page 14: ...14 III Pre Installation and Boiler Mounting G General continued Figure 5 Boiler Stacking...
Page 47: ...47 VI Water Piping and Trim continued Figure 28 Near Boiler Piping Heating Only...
Page 71: ...71 IX System Start up continued Figure 47 Operating Instructions...
Page 122: ...122 XIII Repair Parts continued...
Page 126: ...126 XIII Repair Parts continued...
Page 129: ...129 XIII Repair Parts continued 10A 10B 10C 10D 10G...
Page 134: ...134...
Page 135: ...135...