133
Altitude
Model
Fuel
Recommended CO
2
Range
Percentage Derate
(approx. per 1000 ft)
2,001 ft
to 4,500 ft
PHNTM399C
NG
8.6-9.2
2.3%
LP
9.4-10.2
PHNTM500C
NG
8.7-9.2
4.1%
LP
9.8-10.1
4,001 ft
to 6,000 ft
PHNTM399C
NG
8.6-9.2
2.3%
LP
9.4-10.2
PHNTM500C
NG
8.7-9.2
4.1%
LP
9.8-10.1
6,001 ft
to 7,800 ft
PHNTM399C
NG
8.6-9.2
2.2%
LP
9.4-10.0
PHNTM500C
NG
8.7-9.2
3.6%
LP
No Application
No Application
7,801 ft
to 10,100 ft
PHNTM399C
NG
8.6-9.2
2.2%
LP
9.4-9.8
PHNTM500C
NG
8.7-9.2
3.4%
LP
No Application
No Application
NOTE
: De-rate’s per 1000 ft are approximate
**Based on minimum vent length**
Appendix A - Instructions for High Altitude Installations Above 2000 ft.
(continued)
Table S2: Phantom X Altitude Adjustments