Crown Boiler 16 Series and Installation And Operating Instructions Manual Download Page 28

28

26

X  Control System Wiring

WARNING

All wiring and grounding must be done in accordance with the authority having jurisdiction or, in the absence of such
requirements, with the National Electrical Code (ANSI/NFPA 70).

1) Provide the boiler with a dedicated branch circuit with a fused disconnect. The minimum rating of this circuit

must be 15A.

2) Locate the supplied wire harnesses and wire the boiler following the appropriate wiring diagram in Figures 21 or

22.  Use 14 gauge wire for all 120 volt wiring to circulators, low water cut-offs and auxiliary manual reset hi limits
switches supplied by others.  The junction box located on the inside right side jacket panel is to become the hub for
all limit and low water cut-off wiring.  All 120 volt boiler wiring must be enclosed in conduit.

3) Make sure that all single pole switches and safety controls supplied by others are in the “hot” (ungrounded) side of

the circuit.

4) If a LWCO and or manual reset limit are used, wire them so that they break the 120 volt “Hot” connection to the

boiler.  Do not install these devices in the 24 volt factory wiring.

5) When wiring the optional vent damper attach the quick connect end of the supplied wire harness to the mounting

bracket on the vent and plug the quick connect into the receptacle on the vent damper.  Attach the BX cable
connector located on the other end of the harness to one of the knockouts on the jacket top panel.  Remove the
factory installed jumper plug from the vent damper receptacle located in the vestibule and insert the plug from the
vent damper harness into the vent damper receptacle.  Cut the jumper wire on the jumper plug and discard it.

6) The 24 volt “thermostat / operating control” shown in Figures 21 and 22 is not supplied.  It is the control that turns

the boiler on in response to a call for heat.   Follow the thermostat / operating control instructions for placement
and wiring.   Provide Class II circuit between the thermostat / operating control and the boiler.  Wire the thermostat
or operating control across terminals ‘G’ and ‘R’ on the Honeywell 8285D Control Center as shown in Figures 21
and 22.  Set the heat anticipator on the thermostat to match the setting listed on the ignition control.

7) Attach the line voltage or “hot” side of the circulator motor supplied by others to the yellow wire from terminal

3 on the R8222U relay located on the Honeywell R8285D Control Center.  Attach the neutral side of the circulator
to the common leads in the junction box and ground as required by the circulator manufacturer.  See Figures 21 and
22 for details.

Sequence of Operation – Vent Damper (If Used)

1) The vent damper is continuously powered at terminal 1.

2) On a call for heat, the damper relay coil is energized through terminal 2 if all the limits ahead of the damper are

satisfied.

3) The relay coil closes contacts which energize the damper motor, causing the damper to open.

4) When the damper blade reaches the fully open position, power is sent back to the ignition circuit through terminal 3

and the damper motor is de-energized.

DANGER

Do not attempt to reuse the jumper plug on boilers installed with vent dampers.  Flue gas spillage can occur resulting
in severe injury or death.

Summary of Contents for 16 Series and

Page 1: ...raft Water Boilers INSTALLATION AND OPERATING INSTRUCTIONS These instructions must be affixed on or adjacent to the boiler WARNING Improper installation adjustment alteration service or maintenance ca...

Page 2: ...2...

Page 3: ...X Control System Wiring 26 A Standard 27 B CSD 1 27 XI Start Up Checkout 31 XII Service Maintenance 35 XIII Parts 37 I Product Description The Series 16 boiler is a cast iron hot water boiler designed...

Page 4: ...4 2 II Specifications...

Page 5: ...at the correct altitude 6 Follow the instructions in Section V to assemble the boiler IV Locating the Boiler 1 Do not install this boiler directly on a combustible floor This boiler may be installed...

Page 6: ...stall this boiler in a location where gasoline or other flammable vapors or liquids will be stored or used Do not install this boiler in an area where large amounts of airborne dust will be present su...

Page 7: ...Ove r A ll De p th Jack e t Ove r A ll He ig h t Flo o r T o T o p Of Jack e t Bo ile r V o lu m e Ft3 M in im u m Ro o m V o lu m e Ft3 16 325 23 3 4 32 7 16 32 1 2 14 5 231 8 16 390 27 1 2 32 7 16...

Page 8: ...ase hold down bolts used to anchor the assembly to the skid 5 Exercise care to avoid dropping the boiler while removing it from the skid 6 Leak test the heat exchanger before installing the jacket tri...

Page 9: ...well from the Combination Boiler Parts and Control Carton Insert the immersion well in tapping D See Figure 4 If a second limit or operating control is used it is recommended that it be installed in...

Page 10: ...metal screws four per side as shown in Figure 6 4 On the front of the boiler insert the jacket vestibule panel between the left and right jacket side panels Align the screw holes located on the side f...

Page 11: ...ontrol module to the ignition module base using 4 8 x 1 2 sheet metal screws 6 Connect the green ground wire from the pilot assembly to terminal number 4 Burner GND on the ignition control module 7 Co...

Page 12: ...12 10 Figure 6 Jacket Assembly...

Page 13: ...13 11 Figure 7 Gas Train Standard Build Figure 8 Gas Train CSD 1 Build 16 455 16 520 16 585...

Page 14: ...wiring instructions c Temperature Pressure Gauge Install the T P gauge in tapping H Tapping H is located on the supplied 2 NPT x 10 supply nipple See Figure 9 DO NOT TIGHTEN THE GAUGE BY ITS CASE d L...

Page 15: ...n 3 Determine total input of all fuel burning appliances in the boiler room space Add inputs of all fuel burning appliances in the boiler room space and round the result to the next highest 1000 Btu p...

Page 16: ...area of 1 square inch per 4 000 Btu per hour input of all fuel burning appliances in the boiler room space but not less than 100 square inches The cross sectional area of the duct shall be the same a...

Page 17: ...17 15 Figure 11 All Air From Outdoors Ventilated Crawl Space Attic Figure 12 All Air From Outdoors Via Ventilated Attic Figure 13 All Air From Outdoors Using Openings Into Boiler Room...

Page 18: ...18 16 Figure 14 All Air From Outdoors Using Horizontal Ducts Into The Boiler Room...

Page 19: ...There are two conditions under which an exterior chimney may be used In some very restrictive cases Series 16 boilers may be vented into an exterior ceramic lined masonry chimney See the National Fuel...

Page 20: ...ch assembly from top of boiler Uncoil power cord b Position mounting bracket onto lower edge of draft hood skirt Locate center tooth with 10 sheet metal screw on outside and other two teeth inside dra...

Page 21: ...The damper wire harness is shipped loose One end of the harness is provided with a quick connect fitting and the other end of the harness is provided with a connector nut Attach the end with the conne...

Page 22: ...ance not connected to the common venting system Turn on any exhaust fans such as range hoods and bathroom exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close firep...

Page 23: ...ve to the end of the coupling c Circulator Required The best circulator location is usually on the supply piping just downstream of the expansion tank as shown in Figure 18 d Expansion Tank Required I...

Page 24: ...hown in Figure 18 will minimize the amount of time that the boiler operates with return temperatures below 120 F on these systems A bypass is installed as shown to divert some supply water directly in...

Page 25: ...25 23 Figure 18 Standard Boiler Piping...

Page 26: ...26 Figure 19 Recommended Piping for Combination Heating Cooling Refrigeration System 24...

Page 27: ...own 3 Be sure to use a pipe thread compound pipe dope compatible with the fuel type to be used i e NG natural gas or LP liquefied petroleum for all gas line connections 4 The use of teflon tape is not...

Page 28: ...ted in the vestibule and insert the plug from the vent damper harness into the vent damper receptacle Cut the jumper wire on the jumper plug and discard it 6 The 24 volt thermostat operating control s...

Page 29: ...ntrol contacts will be open 2 Upon a call for heat the operating control will make and the vent damper if used will open Simultaneously 120 volts will be applied to the circulator 3 24 volts will then...

Page 30: ...30 28 Figure 21 Series 16 Standard Boiler Wiring...

Page 31: ...31 29 Figure 22 Series 16 CSD 1 Boiler Wiring...

Page 32: ...ation when flue gas spillage caused by a complete vent blockage occurs The circulator continues to operate and the vent damper if used remains open with a call for heat If the blocked vent switch is a...

Page 33: ...nt damper if used has fully opened 7 Start the boiler using the appropriate lighting instructions for the gas valve on the boiler on page 34 NOTE SAFE LIGHTING AND OTHER PERFORMANCE CRITERIA WERE MET...

Page 34: ...ner and main burners should stop firing 13 Check the manifold pressure and adjust if necessary To do this use the following procedure a Connect a manometer to the inlet pressure tap on the gas valve S...

Page 35: ...emperature to increase to high limit setting The burners should shut down the circulator continues running and the vent damper if used closes Allow the boiler water temperature to drop below high limi...

Page 36: ...to lowest setting 3 Turn off all electric power to the appliance 4 This appliance is equipped with an ignition device which automatically lights the pilot Do try to light the pilot by hand not 5 Remo...

Page 37: ...a soft bristle brush and then vacuuming out any debris through the venturi opening 5 Inspect the pilot assembly Clean any deposits found on the electrode and grounding strap The ideal gap between the...

Page 38: ...ch on the skirt of the draft hood as shown in Figure 16 18 Reconnect the vent system including the optional vent damper if previously installed WARNING SOOT DEPOSITS IN THE FLUE PASSAGES ARE A SIGN TH...

Page 39: ...urner orifice 37 16 325 16 390 16 455 16 520 16 585 1 EACH 1 EACH 1 EACH 1 EACH 16 325 1 1 1 1 260206 260136 500506 260035 16 390 1 1 1 1 260207 260137 500507 260036 16 455 1 1 1 1 260208 260138 50050...

Page 40: ...40 Figure 26 Exploded View Base Parts Manifold 38...

Page 41: ...AS INCLUDED IN PILOT ASSEMBLY 1 1 1 1 1 17b KF16 PILOT ORIFICE LP GAS INCLUDED IN PILOT ASSEMBLY 1 1 1 1 1 17c 1 4 COMPRESSION FERRULE 3501150 1 1 1 1 1 18 10 32 X 3 16 MACHINE SCREW 146 95 301 2 2 2...

Page 42: ...42 Figure 27 Exploded View Base Heat Exchanger Flue Collector Assembly 40...

Page 43: ...520 260129 1 16 585 260130 1 32 5 16 18 X 1 1 2 HEX HEAD CAP SCREW 900415 6 6 6 6 6 33 3 8 FLAT WASHER 90 036 6 6 6 6 6 34 5 16 18 HEX NUT 90 910 6 6 6 6 6 35 5 16 18 X 3 4 HEX HEAD CAP SCREW 900400...

Page 44: ...44 42 Figure 28 Exploded View Jacket...

Page 45: ...43 VESTIBULE PANEL 44 TOP JACKET PANEL 45 JACKET DOOR PANEL 16 325 16 390 16 455 16 520 16 585 47 DOOR KNOB 90 210 2 2 2 2 2 48 8 32 X 1 4 H W H SCREW 90 211 2 2 2 2 2 49 VERTICAL JACKET CLIP 800341...

Page 46: ...46 44 Figure 29 Exploded View Trim Control Components...

Page 47: ...LY 3503107 1 1 1 RV12L PILOT REGULATOR NAT LP CSD 1 ONLY 3503115 1 1 1 900460 1 1 1 WIRE HARNESS ASSEMBLY CSD 1 ONLY 9605920 1 1 1 GAS VALVE HARNESS CSD 1 ONLY 9605900 1 1 1 ALARM HARNESS CSD 1 ONLY P...

Page 48: ...48 PN 980416 S 1 6 0 6 0 4 Tel 215 535 8900 Fax 215 535 9736 www crownboiler com Manufacturer of Hydronic Heating Products P O Box 14818 3633 I Street Philadelphia PA 19134...

Reviews: