21
b) Vent damper is factory shipped having approximately ¾” diameter hole in the vent damper blade, which
must be
left open
for boilers equipped with standing pilot, and should be plugged on boilers with an intermittent pilot,
using the plug supplied with the damper.
Mount the vent damper on the flue collar without modification to either and secure with sheet metal screws.
Make sure screws do not interfere with damper blade operation. Vent damper blade position indicator must be
visible to users.
c) The damper wire harness is shipped loose. One end of the harness is provided with a quick connect fitting and
the other end of the harness is provided with a connector nut. Attach the end with the connector nut to the top
jacket panel using one of the 1/2” knockouts and plug the polarized connectors together. At the vent damper,
plug the loose end of the harness into the damper and attach the quick connector to the bracket on the vent
damper motor.
d) Install vent connector pipe and vent fittings from vent damper outlet to chimney or gas vent. Secure with sheet
metal screws and support as required.
19
Figure 17: Vent Damper Installation Details
Figure 16: Blocked Vent Switch Installation Details
Summary of Contents for 16 Series and
Page 2: ...2...
Page 4: ...4 2 II Specifications...
Page 12: ...12 10 Figure 6 Jacket Assembly...
Page 13: ...13 11 Figure 7 Gas Train Standard Build Figure 8 Gas Train CSD 1 Build 16 455 16 520 16 585...
Page 18: ...18 16 Figure 14 All Air From Outdoors Using Horizontal Ducts Into The Boiler Room...
Page 25: ...25 23 Figure 18 Standard Boiler Piping...
Page 26: ...26 Figure 19 Recommended Piping for Combination Heating Cooling Refrigeration System 24...
Page 30: ...30 28 Figure 21 Series 16 Standard Boiler Wiring...
Page 31: ...31 29 Figure 22 Series 16 CSD 1 Boiler Wiring...
Page 40: ...40 Figure 26 Exploded View Base Parts Manifold 38...
Page 42: ...42 Figure 27 Exploded View Base Heat Exchanger Flue Collector Assembly 40...
Page 44: ...44 42 Figure 28 Exploded View Jacket...
Page 46: ...46 44 Figure 29 Exploded View Trim Control Components...