Crown Boiler 16 Series and Installation And Operating Instructions Manual Download Page 23

23

VIII System Piping

A.  Standard Heating System Piping

1) Figure 18 shows typical boiler system connections on a single zone system.  Additional information on hydronic

system design may be found in 

Installation of Residential Hydronic Systems

 (Pub. #200) published by the Hydronics

Institute in Berkeley Heights, NJ.  The components in this system and their purposes are as follows:

a. Relief valve (Required) - Install a 3/4” NPT x 3-1/2” lg. nipple in tapping “C” located on the left side of the

boiler.  Mount the relief valve on the end of the nipple as shown in Figure 1.  The relief valve shipped with the
boiler is set to open at 30 psi.  This valve may be replaced with one having a pressure up to the “MAWP, WATER”
shown on the rating plate.  If the valve is replaced, the replacement must have a relief capacity in excess of the DOE
heating capacity for the boiler.
Pipe the discharge of the relief valve to a location where water or steam will not create a hazard or cause property
damage if the valve opens.  The end of the discharge pipe must terminate in an unthreaded pipe.  If the relief valve
discharge is not piped to a drain it must terminate at least 6 inches above the floor.  Do not run relief valve discharge
piping through an area that is prone to freezing.  The termination of the relief valve discharge piping must be in an
area where it is not likely to become plugged by debris.

b. Drain Valve (Required) - Install a 3/4” NPT x 3-1/2”  nipple in tapping “G” located in the rear of the left end section

of the boiler.  Attach a 3/4” NPT pipe coupling to the end of the nipple and attach the drain valve to the end of the
coupling.

c. Circulator (Required) - The best circulator location is usually on the supply piping just downstream of the expansion

tank as shown in Figure 18.

d. Expansion Tank (Required) - If the expansion tank must be replaced, consult the expansion tank manufacturer’s

literature for proper sizing.

e. Fill Valve (Required) - Either a manual or automatic fill valve may be used.  The ideal location for the fill is at the

expansion tank.  On large systems with an automatic fill valve, it is recommended that a small water meter be
installed in the make-up water line to monitor the amount of water added to the system.

f. Automatic Air Vent (Required) - At least one automatic air vent is required and should be located at the expansion

tank.  Manual vents will usually be required in other parts of the system to remove air during initial fill.

g. Low Water Cut-Off (Required in some situations) - A low water cutoff is required when the boiler is installed above

radiation.  In addition, some codes such as ASME CSD-1 require low water cutoffs.  Codes may also require that

CAUTION

• INSTALL  BOILER  SO  THAT  THE  GAS  IGNITION  SYSTEM  COMPONENTS  ARE  PROTECTED

FROM WATER  (DRIPPING,  SPRAYING,  RAIN,  ETC.)  DURING  APPLIANCE  OPERATION  AND
SERVICE (CIRCULATOR  REPLACEMENT,  ETC.).

• OPERATION  OF  THIS  BOILER  WITH  CONTINUOUS  RETURN  TEMPERATURES  BELOW  120°F

CAN CAUSE  SEVERE  HEAT  EXCHANGER  CORROSION  DAMAGE.

• OPERATION  OF  THIS  BOILER  IN  A  SYSTEM  HAVING  SIGNIFICANT  AMOUNTS  OF  DISSOLVED

OXYGEN  CAN  CAUSE  SEVERE  HEAT  EXCHANGER  CORROSION  DAMAGE.

• DO  NOT  USE  TOXIC  ADDITIVES,  SUCH  AS  AUTOMOTIVE  ANTIFREEZE,  IN  A  HYDRONIC

SYSTEM.

DANGER

PIPE  RELIEF  VALVE  DISCHARGE  TO  A  SAFE  LOCATION.

DO  NOT  INSTALL  A  VALVE  IN  THE  RELIEF  VALVE  DISCHARGE  LINE.

DO  NOT  MOVE  RELIEF  VALVE  FROM  FACTORY  LOCATION.

DO  NOT  PLUG  RELIEF  VALVE  DISCHARGE.

21

Summary of Contents for 16 Series and

Page 1: ...raft Water Boilers INSTALLATION AND OPERATING INSTRUCTIONS These instructions must be affixed on or adjacent to the boiler WARNING Improper installation adjustment alteration service or maintenance ca...

Page 2: ...2...

Page 3: ...X Control System Wiring 26 A Standard 27 B CSD 1 27 XI Start Up Checkout 31 XII Service Maintenance 35 XIII Parts 37 I Product Description The Series 16 boiler is a cast iron hot water boiler designed...

Page 4: ...4 2 II Specifications...

Page 5: ...at the correct altitude 6 Follow the instructions in Section V to assemble the boiler IV Locating the Boiler 1 Do not install this boiler directly on a combustible floor This boiler may be installed...

Page 6: ...stall this boiler in a location where gasoline or other flammable vapors or liquids will be stored or used Do not install this boiler in an area where large amounts of airborne dust will be present su...

Page 7: ...Ove r A ll De p th Jack e t Ove r A ll He ig h t Flo o r T o T o p Of Jack e t Bo ile r V o lu m e Ft3 M in im u m Ro o m V o lu m e Ft3 16 325 23 3 4 32 7 16 32 1 2 14 5 231 8 16 390 27 1 2 32 7 16...

Page 8: ...ase hold down bolts used to anchor the assembly to the skid 5 Exercise care to avoid dropping the boiler while removing it from the skid 6 Leak test the heat exchanger before installing the jacket tri...

Page 9: ...well from the Combination Boiler Parts and Control Carton Insert the immersion well in tapping D See Figure 4 If a second limit or operating control is used it is recommended that it be installed in...

Page 10: ...metal screws four per side as shown in Figure 6 4 On the front of the boiler insert the jacket vestibule panel between the left and right jacket side panels Align the screw holes located on the side f...

Page 11: ...ontrol module to the ignition module base using 4 8 x 1 2 sheet metal screws 6 Connect the green ground wire from the pilot assembly to terminal number 4 Burner GND on the ignition control module 7 Co...

Page 12: ...12 10 Figure 6 Jacket Assembly...

Page 13: ...13 11 Figure 7 Gas Train Standard Build Figure 8 Gas Train CSD 1 Build 16 455 16 520 16 585...

Page 14: ...wiring instructions c Temperature Pressure Gauge Install the T P gauge in tapping H Tapping H is located on the supplied 2 NPT x 10 supply nipple See Figure 9 DO NOT TIGHTEN THE GAUGE BY ITS CASE d L...

Page 15: ...n 3 Determine total input of all fuel burning appliances in the boiler room space Add inputs of all fuel burning appliances in the boiler room space and round the result to the next highest 1000 Btu p...

Page 16: ...area of 1 square inch per 4 000 Btu per hour input of all fuel burning appliances in the boiler room space but not less than 100 square inches The cross sectional area of the duct shall be the same a...

Page 17: ...17 15 Figure 11 All Air From Outdoors Ventilated Crawl Space Attic Figure 12 All Air From Outdoors Via Ventilated Attic Figure 13 All Air From Outdoors Using Openings Into Boiler Room...

Page 18: ...18 16 Figure 14 All Air From Outdoors Using Horizontal Ducts Into The Boiler Room...

Page 19: ...There are two conditions under which an exterior chimney may be used In some very restrictive cases Series 16 boilers may be vented into an exterior ceramic lined masonry chimney See the National Fuel...

Page 20: ...ch assembly from top of boiler Uncoil power cord b Position mounting bracket onto lower edge of draft hood skirt Locate center tooth with 10 sheet metal screw on outside and other two teeth inside dra...

Page 21: ...The damper wire harness is shipped loose One end of the harness is provided with a quick connect fitting and the other end of the harness is provided with a connector nut Attach the end with the conne...

Page 22: ...ance not connected to the common venting system Turn on any exhaust fans such as range hoods and bathroom exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close firep...

Page 23: ...ve to the end of the coupling c Circulator Required The best circulator location is usually on the supply piping just downstream of the expansion tank as shown in Figure 18 d Expansion Tank Required I...

Page 24: ...hown in Figure 18 will minimize the amount of time that the boiler operates with return temperatures below 120 F on these systems A bypass is installed as shown to divert some supply water directly in...

Page 25: ...25 23 Figure 18 Standard Boiler Piping...

Page 26: ...26 Figure 19 Recommended Piping for Combination Heating Cooling Refrigeration System 24...

Page 27: ...own 3 Be sure to use a pipe thread compound pipe dope compatible with the fuel type to be used i e NG natural gas or LP liquefied petroleum for all gas line connections 4 The use of teflon tape is not...

Page 28: ...ted in the vestibule and insert the plug from the vent damper harness into the vent damper receptacle Cut the jumper wire on the jumper plug and discard it 6 The 24 volt thermostat operating control s...

Page 29: ...ntrol contacts will be open 2 Upon a call for heat the operating control will make and the vent damper if used will open Simultaneously 120 volts will be applied to the circulator 3 24 volts will then...

Page 30: ...30 28 Figure 21 Series 16 Standard Boiler Wiring...

Page 31: ...31 29 Figure 22 Series 16 CSD 1 Boiler Wiring...

Page 32: ...ation when flue gas spillage caused by a complete vent blockage occurs The circulator continues to operate and the vent damper if used remains open with a call for heat If the blocked vent switch is a...

Page 33: ...nt damper if used has fully opened 7 Start the boiler using the appropriate lighting instructions for the gas valve on the boiler on page 34 NOTE SAFE LIGHTING AND OTHER PERFORMANCE CRITERIA WERE MET...

Page 34: ...ner and main burners should stop firing 13 Check the manifold pressure and adjust if necessary To do this use the following procedure a Connect a manometer to the inlet pressure tap on the gas valve S...

Page 35: ...emperature to increase to high limit setting The burners should shut down the circulator continues running and the vent damper if used closes Allow the boiler water temperature to drop below high limi...

Page 36: ...to lowest setting 3 Turn off all electric power to the appliance 4 This appliance is equipped with an ignition device which automatically lights the pilot Do try to light the pilot by hand not 5 Remo...

Page 37: ...a soft bristle brush and then vacuuming out any debris through the venturi opening 5 Inspect the pilot assembly Clean any deposits found on the electrode and grounding strap The ideal gap between the...

Page 38: ...ch on the skirt of the draft hood as shown in Figure 16 18 Reconnect the vent system including the optional vent damper if previously installed WARNING SOOT DEPOSITS IN THE FLUE PASSAGES ARE A SIGN TH...

Page 39: ...urner orifice 37 16 325 16 390 16 455 16 520 16 585 1 EACH 1 EACH 1 EACH 1 EACH 16 325 1 1 1 1 260206 260136 500506 260035 16 390 1 1 1 1 260207 260137 500507 260036 16 455 1 1 1 1 260208 260138 50050...

Page 40: ...40 Figure 26 Exploded View Base Parts Manifold 38...

Page 41: ...AS INCLUDED IN PILOT ASSEMBLY 1 1 1 1 1 17b KF16 PILOT ORIFICE LP GAS INCLUDED IN PILOT ASSEMBLY 1 1 1 1 1 17c 1 4 COMPRESSION FERRULE 3501150 1 1 1 1 1 18 10 32 X 3 16 MACHINE SCREW 146 95 301 2 2 2...

Page 42: ...42 Figure 27 Exploded View Base Heat Exchanger Flue Collector Assembly 40...

Page 43: ...520 260129 1 16 585 260130 1 32 5 16 18 X 1 1 2 HEX HEAD CAP SCREW 900415 6 6 6 6 6 33 3 8 FLAT WASHER 90 036 6 6 6 6 6 34 5 16 18 HEX NUT 90 910 6 6 6 6 6 35 5 16 18 X 3 4 HEX HEAD CAP SCREW 900400...

Page 44: ...44 42 Figure 28 Exploded View Jacket...

Page 45: ...43 VESTIBULE PANEL 44 TOP JACKET PANEL 45 JACKET DOOR PANEL 16 325 16 390 16 455 16 520 16 585 47 DOOR KNOB 90 210 2 2 2 2 2 48 8 32 X 1 4 H W H SCREW 90 211 2 2 2 2 2 49 VERTICAL JACKET CLIP 800341...

Page 46: ...46 44 Figure 29 Exploded View Trim Control Components...

Page 47: ...LY 3503107 1 1 1 RV12L PILOT REGULATOR NAT LP CSD 1 ONLY 3503115 1 1 1 900460 1 1 1 WIRE HARNESS ASSEMBLY CSD 1 ONLY 9605920 1 1 1 GAS VALVE HARNESS CSD 1 ONLY 9605900 1 1 1 ALARM HARNESS CSD 1 ONLY P...

Page 48: ...48 PN 980416 S 1 6 0 6 0 4 Tel 215 535 8900 Fax 215 535 9736 www crownboiler com Manufacturer of Hydronic Heating Products P O Box 14818 3633 I Street Philadelphia PA 19134...

Reviews: