Page 26
P223E Output 3 Pulse Timer -
(Default = 20)
P224E Output 4 Pulse Timer -
(Default = 20)
P225E Output 5 Pulse Timer -
(Default = 20)
P226E Output 6 Pulse Timer -
(Default = 20)
P227E Output 7 Pulse Timer -
(Default = 20)
P228E Output 8 Pulse Timer -
(Default = 20)
RADIO ZONE CODE LOAD
To load a radio device as a zone input on the panel, press the appropriate address number (eg
P604E for Zone 4). The keypad buzzer will beep once a second to indicate learn mode has been
initiated and the Led on the RX-40 board will flash. The radio device you wish to load must transmit a
signal within 30 seconds of entering learn mode otherwise the panel will time out and no code will be
loaded. If a valid code is received within the 30 seconds the keypad will give 3 short beeps and exit
learn mode. To remove a loaded radio code at a single address only, enter in the address you wish
to delete the code at eg P604E, then without operating the transmitter and before the 30 second
timer expires press the “Enter” button. This will remove the code loaded against this address (in this
case radio zone 4).
P601E
Load Radio Code for Zone 1
P602E
Load Radio Code for Zone 2
P603E
Load Radio Code for Zone 3
P604E
Load Radio Code for Zone 4
RADIO ZONE DETECTOR OPTIONS
RADIO ZONE DETECTOR OPTIONS
-
P231E-P234E - Default= 0
This block of addresses (P231E - P234E) are used to select the type of detector to be used on the radio zone
input and allow functions such as battery low, tamper and normal alarm to be correctly recognized. To make the
radio zone work you must also tell the zone input that it is a radio zone (P134E-zones 1-4).
P231E-Zone 1 Options 1E
Crow AE series battery Low
2E
Crow AE series Radio Reed Switch
3E
Crow Merlin PIR (supervised signal ignored)
4E
Crow Merlin PIR (supervised signal active)
11E
Ness Radio devices Battery Low
12E
Ness Radio Reed Switch
21E
Electronics Line Cougar Radio PIR
31E
Visonic K900 Radio PIR
32E
Visonic Powercode Devices (supervised signal ignored)
33E
Visonic Powercode Devices (supervised signal active)
Option 1
Crow AE Series Battery Low
- If a Crow (AE) radio pendant or PIR is used on the PW-4 radio zone
input, setting this bit allows the panel to correctly recognize the battery low signal from Crow devices.
Option 2
Crow AE Series Radio Reed Switch
- If a Crow (AE) radio reed switch is used on the PW-4 radio
zone input, setting this bit allows the panel to correctly recognize the battery low signal from the Crow
device. This bit also recognizes the open and closed signals from the reed switch so the zone Led
can follow the correct state of the reed switch (i.e. open or closed)
Option 3
Crow Merlin PIR (unsupervised) -
If a Crow Merlin radio PIR is used on the PW-4 radio zone input,
setting this bit allows the panel to correctly recognize the alarm, tamper & battery low signal from the
device. The automatic supervised signal sent every 40 minutes by the PIR is ignored in this mode.
Option 4
Crow Merlin PIR (supervised) -
If a Crow Merlin radio PIR is used on the PW-4 radio zone input,
setting this bit allows the panel to correctly recognize the alarm, tamper & battery low signal from the
device. Setting this option on also starts a 4 hour timer for the supervised signal. The 4 hour timer is
constantly being reset while valid supervised signals are being received every 40 minutes. If no
supervised signals are received from the PIR within the 4 hour period, a supervised alarm is
generated.
20
O/P 1 Pulse Time
LearnRadioZone1
Learning