background image

ELECTRONIC ENGINEERING LTD

.

 

     

4 Zone Control  Panel Communicator 

 

PowerWave- 4 

P/N 7111346  Rev. B  M.E/Y.S/N.A 

 Version  8.63  07/2002 

Installation and   

          Programming Guide 

Page 1 

 

1

2

3

4

A

5

6

7

8

B

Ready-Byp

S yst

e m

Trouble

P r o g

r a m

7

4

1

2

3

5

6

9

8

0

E NT

E R

P RO

G RA

M

B YP

A SS

STAY

ARM

CO NT RO L

MEM

ORY

P

A

N

IC

Summary of Contents for PowerWave-4

Page 1: ...lCommunicator PowerWave 4 P N 7111346 Rev B M E Y S N A Version 8 63 07 2002 Installationand ProgrammingGuide Page 1 1 2 3 4 A 5 6 7 8 B Ready Byp System Trouble Program 7 4 1 2 3 5 6 9 8 0 ENTER PROG...

Page 2: ...TWO TRIGGER TIMER 24 DAY MODE TIMER TO KEYPAD BUZZER 25 OUTPUT TIMING OPTIONS 25 LOADING RADIO ZONES 26 RADIO ZONE OPTIONS 26 LOADING RADIO PENDANTS 27 RADIO PENDANT OPTIONS A 28 RADIO PENDANT OPTION...

Page 3: ...In Line Out AC AC Heat sink EXPANSION 1 6A F1 PowerWave 4 230V AC Input Red Blk _ Battery From Street To Phone Mains Earth Keypad Pos Neg Gnd Ant Clock Data RX 40 Receiver _ Passive Infra Red Detector...

Page 4: ...of Line EOL No Tamper Type 4 End of Line EOL With open short circuit Tamper The following table shows end of line resistor configurations The reference to LEDS in bold below relate to the program opt...

Page 5: ...the system LED refer to the View Memory chart on page 9 for more details LINE IN This pair of terminals is used to connect the PW 4 to the incoming telephone line from the street The communicator use...

Page 6: ...ction must be disconnected before the power is disconnected Similarly when reconnecting the dialer it is necessary to power up the Alert before connecting the dialer to the Telecom Network Connection...

Page 7: ...splay system menus and prompts trouble indications time date clock viewable event buffer all system parameters programming customizable zone labeling LED KEYPAD LED indicators READY ARMED TROUBLE 4 Ke...

Page 8: ...via a 4 wire data security cable A maximum of 8 keypads can be connected each wired in parallel The maximum recommended cable using standard 0 2mm security cable is 50m Cable runs exceeding this dista...

Page 9: ...hing DURESS ALARM Duress Alarm TROUBLE AREA A B On Steady Flashing SUPERVISED RADIO ALARM Supervised Radio Passive Infra Red SYSTEM TROUBLE LED s 1 4 On Steady Flashing Flashing ZONE INACTIVITY ALARM...

Page 10: ...default each keypad comes addressed as 1 Switches A B and C at ON position To assign a keypad as address 2 change switch A to OFF position To assign a keypad as address 3 change switch B to OFF posit...

Page 11: ...at the end of a button sequence The CONTROL button if enabled is used to isolate day zone audible alarms if temporarily not required and or to directly control outputs if programmed ICON LED INDICATO...

Page 12: ...light will Flash Note Default Installer Code Code 11 is 000000 You are now in Installer Program Mode Any program addresses may be viewed or changed in this mode ACCESS TO CLIENT PROGRAM MODE FROM RUN...

Page 13: ...ode you must first be in client or installer program mode then select the address from 1 10 If there is already a code programmed at this address it will be flashed back to you Now enter the code then...

Page 14: ...over relay contacts OUTPUT OPTIONS A P31E P38E This block of addresses P31E P38E are used to map output modifiers to each of the 8 outputs available on the PW 4 P31E 1E Invert output Default off 2E Fl...

Page 15: ...nished the operator then presses the Enter button to cancel the Control mode and return to normal To operate the output s via a telephone please refer to the instructions supplied with the voice board...

Page 16: ...lows individual zones to be mapped to selected outputs The default setting is that zones 1 4 will turn on all outputs 1 8 when in alarm P51E Zone Alarms to Output 1 Options Zones 1 4 Default 1 4 P52E...

Page 17: ...Output 2 Options Zones 1 4 Default None P83E Day Zones to Output 3 Options Zones 1 4 Default None P84E Day Zones to Output 4 Options Zones 1 4 Default None P85E Day Zones to Output 5 Options Zones 1...

Page 18: ...E This address allows modification of how Partition A arming STAY and control keys work at the keypad P110E 1E ARM button required before code to set Default off 2E STAY button required before code to...

Page 19: ...3E Disarm status to output Default off P113E ON 4E Pendant chirps for Arm to output Default off 5E Pendant chirps for Stay Mode On to output Default off 6E Pendant chirps for Disarm to output Default...

Page 20: ...ore a code is entered to set Area B Stay Mode If a keypad is assigned to both Partitions this option should be set to allow individual arming of Stay Mode for each area Option 3 CODE required to set I...

Page 21: ...isarmed The output reset time should be set to zero Option 3 Disarm indication to output This option will turn the output on when Area B is Disarmed The output will turn on when the Area B is disarmed...

Page 22: ...ult Led Off All Zones NC Normally Closed By turning the LED on for zone 1 at this address the panel is now looking for a Normally Open NO contact on the zone 4K7 P134E Radio Zone Input Zones 1 4 Defau...

Page 23: ...which zones can be assigned as Lockout Zones A Lockout Zone will only cause the alarm output to sound once during and armed period If the lockout function is not programmed then the zone can cause the...

Page 24: ...y works during the disarmed state and is accumulative which means that if a zone does not trip at least once during a disarm period the inactivity timer is not reset for that zone and will continue wi...

Page 25: ...ON time is how long an output will be delayed before turning on following an alarm condition P201E Output 1 Delay On Time Default 0 Sec P202E Output 2 Delay On Time Default 0 Sec P203E Output 3 Delay...

Page 26: ...ries battery Low 2E Crow AE series Radio Reed Switch 3E Crow Merlin PIR supervised signal ignored 4E Crow Merlin PIR supervised signal active 11E Ness Radio devices Battery Low 12E Ness Radio Reed Swi...

Page 27: ...g this bit allows the panel to correctly recognize the alarm tamper battery low signal from the device Setting this option on also starts a 4 hour timer for the supervised signal The 4 hour timer is c...

Page 28: ...oth partitions if required Option 3 Pendant can Arm This option assigns the Arm function to a pendant The partition s it will arm has to be selected at options 1 2 Option 4 Pendant can Disarm This opt...

Page 29: ...n turn it off Option 3 Visonic Powercode Battery Low If a Visonic Powercode Transmitter with battery low monitoring is used on the PW 4 setting this option will allow the battery signal to be correctl...

Page 30: ...public area P174E Keypads with the Panic Buttons 1 3 or CHIME CONTROL Enabled Option keypad 1 8 Default None KEYPAD RADIO PANIC ALARM TO KEYPAD BUZZER The two Keypad panic functions P173E or P174E plu...

Page 31: ...e keypads If a silent medical alarm is required the option must be turned off at this address For an audible Medical Beep at the keypad s turn this option on P179E Medical Alarm to Keypad Buzzer Optio...

Page 32: ...Fail Test Default off 4E Arm only if sealed Default on 5E No audible keypad beep on supervised radio fault Default off 6E No audible keypad beep for zone Inactivity Timeout Default off 7E Control butt...

Page 33: ...alarm the duress digit must be entered before a valid user code eg If the code was 123 and the duress number was 4 then entering a code of 4123 Enter would create a duress alarm P230E Duress Digit Va...

Page 34: ...ly P622E Restore all Program Addresses from 20 199 to Default P623E Restore all Program Addresses from 200 399 to Default P624E Restore all Program Addresses from 500 599 to Default P625E Restore all...

Page 35: ...nal EPROM memory card DTU Data Transfer Unit which can be plugged into the expansion socket on the control board P628E Write to EEPROM DTU Board READ FROM EEPROM DTU BOARD This address P629E is used t...

Page 36: ...in coming call in two ways The first is to set the auto answer ring count to a convenient number P249E and let the phone ring until this number is reached at which time the panel will answer the call...

Page 37: ...io battery low is detected the panel can report this alarm to a central monitoring company if this option is on Option 5 Report System Tamper If a control panel tamper is detected the panel can report...

Page 38: ...Mode Arm Disarm If this option is on then all Stay Mode Arm Disarm signals will be reported to a central Monitoring Station if Contact ID or 4 2 is set as the reporting format Option 3 Send unset afte...

Page 39: ...for each telephone number P245E Maximum Dial Attempts for Ph 1 Value 0 99 Default 20 P246E Maximum Dial Attempts for Ph 2 Value 0 99 Default 20 P247E Maximum Dial Attempts for Ph 3 Value 0 99 Default...

Page 40: ...e from the monitoring station must be 1400 hz and the transmit tone from the panel will be at 1900hz at 10 pulses per second Option 7 4 2 10 pps This option transmits a 4 digit account code followed b...

Page 41: ...kes a call it looks for dial tone before making the call If no dial tone is detected the panel hangs up and attempts another call The panel will do this 3 times and if dial tone is still not detected...

Page 42: ...t 120 FIRE ALARM CONTACT ID CODE This address P330E is used to set the Contact ID code that a Keypad Fire 4 6 alarm will transmit P330E Keypad Fire Alarm Contact ID Code 3 Digit Number Default 110 MED...

Page 43: ...ASSED 4 2 CODE This block of addresses P581E P584E are used to set the 4 2 code that a Zone will transmit if it is manually or automatically excluded at the time of Arming P581E Zone 1 Bypassed 4 2 Co...

Page 44: ...ser 4 4 2 Code 2 Digit Number Default 44 P545E Armed by User 5 4 2 Code 2 Digit Number Default 45 P546E Armed by User 6 4 2 Code 2 Digit Number Default 46 P547E Armed by User 7 4 2 Code 2 Digit Number...

Page 45: ...lt 72 P573E Disarmed by Radio User 3 4 2 Code 2 Digit Number Default 73 P574E Disarmed by Radio User 4 4 2 Code 2 Digit Number Default 74 P575E Disarmed by Radio User 5 4 2 Code 2 Digit Number Default...

Page 46: ...en record the remote control messages eg if you have 9 alarm messages recorded before the remote control messages the value entered at this address must be 10 A value other than 0 must be entered at t...

Page 47: ...s will occur at the start finish of daylight saving Also if a Domestic or Voice mode alarm is initiated but not reset or kissed off when the test time comes around the dialer will attempt to report th...

Page 48: ...P25E User Options Code 5 Default 1 6 4 Code can Disarm Area Page 14 P26E User Options Code 6 Default 1 6 5 Code can arm Stay Mode Page 14 P27E User Options Code 7 Default 1 6 6 Code can disarm Stay Mo...

Page 49: ...P67E Stay Mode Zone Alarms 1 4 to Output 7 Default None Page 16 P68E Stay Mode Zone Alarms 1 4 to Output 8 Default None Page 16 Mapping 24 Hour Zone Alarms To Outputs P71E 24 Hour Zone Alarms 1 4 to...

Page 50: ...ed Before Code to Set Stay Mode 3 Code required to Set 4 Arm Button can disarm during Exit Delay 5 Stay Button can disarm Stay Mode at any time 6 No Exit beeps to Keypads in Stay Mode 7 Enable Key swi...

Page 51: ...P141E Non Latching 24 Hour Zone Zones 1 4 Default No zones Page 23 P142E Lockout Zone Zones 1 4 Default No zones Page 23 P143E Day Zone CHIME Zones 1 4 Default No zones Page 23 P144E Permanent Day Zo...

Page 52: ...o fault 6 No audible keypad beep on Zone Inactivity Timeout 7 Control Button Disables Day Zones 8 Silent 24 Hour Zone No Keypad Beep Keypad Partition Assignment P171E Keypads Assigned To Partition A V...

Page 53: ...1 4 Use Group Numbers for Contact ID 5 Send Restores 6 Send Test Calls 7 Spare 8 Spare Dialer Programming Options P185E Dialer options P185E Options Default 1 2 7 Page 36 1 Dialer is Enabled 2 Fax Def...

Page 54: ...Day Mode ON Time Value 0 99 1 10 Seconds Default 20 2 Sec Page 25 P212E Output 2 Day Mode ON Time Value 0 99 1 10 Seconds Default 20 2 Sec Page 25 P213E Output 3 Day Mode ON Time Value 0 99 1 10 Secon...

Page 55: ...or Supervised Timer 0 255 Minutes Default 240 Minutes Page 27 Zone Inactivity Timer P240E Zone Inactivity Timer 0 255 Hours Default 120 Hours Page 24 Telephone Number Reporting Options P241E Reporting...

Page 56: ...0 Sec Page 24 P303E Zone 3 Entry Delay Time Value 0 255 Seconds Default 0 Sec Page 24 P304E Zone 4 Entry Delay Time Value 0 255 Seconds Default 0 Sec Page 24 Output Reset Time P311E Output 1 Reset Tim...

Page 57: ...k Year Value 0 99 Page 33 SETTING DAYLIGHT SAVING START FINISH P408E Daylight Saving Start Sunday Value 0 5 Default 1 0 daylight saving start time disabled Page 33 P409E Daylight Saving Start Month Va...

Page 58: ...11 Page 43 P522E 4 2 Alarm Restore Code for Zone 2 Default 12 Page 43 P523E 4 2 Alarm Restore Code for Zone 3 Default 13 Page 43 P524E 4 2 Alarm Restore Code for Zone 4 Default 14 Page 43 System Tampe...

Page 59: ...53 Page 44 P554E 4 2 Disarm Code for User 4 Default 54 Page 44 P555E 4 2 Disarm Code for User 5 Default 55 Page 44 P556E 4 2 Disarm Code for User 6 Default 56 Page 44 P557E 4 2 Disarm Code for User 7...

Page 60: ...43 P583E 4 2 Bypass Message for Zone 3 Default 23 Page 43 P584E 4 2 Bypass Message for Zone 4 Default 24 Page 43 Automatic Test 4 2 Reporting Code P590E 4 2 Automatic Test Code Default 85 Page 44 Zone...

Page 61: ...ddresses 200 399 to Factory Defaults Page 34 Restore Addresses 500 599 to Factory Defaults P624E Restore Addresses 500 599 to Factory Defaults Page 34 Restore All Radio Zone Pendants to Factory Defaul...

Page 62: ...emote set 407 000 Command Control arm disarm Arm by Keyswitch 409 001 Area A Keyswitch Arm Disarm 409 002 Area B Keyswitch Arm Disarm Arm by Up Download 407 000 Remote PC arm disarm Radio key Panic 12...

Page 63: ...ontained in this manual is correct at the time of printing Crow Electronic Engineering Ltd reserve the right to make changes to the features and specifications at any time without notice in the course...

Page 64: ...Page 64...

Reviews: