FCS - Operation Manual
Use the + or - buttons or press the yellow fields and use the keypad to change the values, for
each analog input. You can select:
A. Input:
Select the analog input number (1 to 60) of the analog input you are setting the
current values for.
mA:
This is the measured input current, what the FCS thinks the current is; this value will
change as you change the A/D values or the 4 - 20 mA source.
A/D @ 4 mA:
While applying 4 mA, change the number until the mA value is 4 mA.
A/D @ 20 mA:
While applying 20 mA, change the number until the mA value is 20 mA.
Press SAVE to save the changes.
9.6 Analog Output Calibration
(requires a 4-20 mA meter)
To calibrate the analog output, use an amp meter and adjust the D/A counts to reach the
required current output values.
To enter the Config Analog IO menu, enter code “3032” on the password screen, select NEXT
and select Analog Output Calibration.