42
© 2022 All rights reserved. Data subject to change without notice.
FCS - Operation Manual
Rev. C | 2022.02
D-ON:
ON Delay is the length of time before the relay is activated after an alarm condition
has been triggered. This is useful for example, if you want the audible buzzer and strobe
to come on at different times, or if the monitored area has frequent gas level readings
that could trigger an alarm but not last very long (such as an idling car in a parking
garage/car park).
D-OFF:
OFF Delay is the length of time after the alarm condition has gone back to normal
and the relay continues to be activated. This is useful for example if you want to allow
extra time for the ventilation of the area. Setting an OFF Delay for a horn, strobe or
audible will be the amount of time that the device will be silenced after having sounded
and the Silence All button on the Silence? screen is pushed.
The Save button will turn green after a change has been made. If you are going through more
relays on the same screen, the system will auto save when you press the + or - to proceed or
return to the next relay number. If you press Home or Back, the change will not be saved. You
can choose to press Save if in doubt.
To continue changing or reviewing the settings for each relay press use the + to proceed to
the next relay number.
8.3 How to Override Relays
This setting allows the relays, the audible and/or horn/strobe to be overridden; either
forced on or forced off for a given length of time. This may be useful in situations where
maintenance is being done or a special event is occurring and requires extra safety
precautions.
Press Menu and enter passcode “2012” to enter the Set Alarm menu. Press Next and select
Relay Override.
Use the + and - buttons or enter the specific relay number by pressing the yellow field and
using the keypad to choose the relay number, Audible, Strobe or Horn you want to override.
Enter the number of minutes (up to a maximum of 999) that you would like the override to be
in effect for.
Use the -H and +H buttons to change by 60 minute/1 hour increments and the -M and +M by
one minute at a time.