© 2022 All rights reserved. Data subject to change without notice.
15
Rev. C | 2022.02
FCS - Operation Manual
Yellow field
If you enter the numeric key pad and change a value but you don’t want to save that value, to
exit without saving changes, press the C to clear. The ENTER button will change to CANCEL.
Press CANCEL to exit.
When a value is changed, the ENTER or SAVE button will turn green, indicating a change
has been made and pressing the green button will commit the change. If you change the
value back to its preceding value, the ENTER or SAVE button will change from green, back to
standard colour.
Many of the channel, relay and priority set up screens have an autosave function. If you are
going through more channels (or relays or priorities) on the same screen, the system will
autosave when you press the + or - to proceed or return to the next channel (relay, priority)
number. If you press Home or Back, the changes will not be saved. The Save button will turn
green after a change has been made and you can choose to press Save if in doubt.
4.2 Accessing the Menu with Passcodes
The main menu structure is broken down by the passcode access entry. Press on the MENU
button to access the Enter Password screen.
These passcodes allow for direct access to the parts of the menu system of interest:
CODE
NAME
DESCRIPTION
1
Test
Test Audible, Test Strobe, Test Relays
Test Analog Outputs (VFD)
1001
Basic
Set Clock, Enable / Disable Data Logging, Set Data
Logging Interval, Modbus® Setup / BACnet® Setup
1014
Display
Configure RDM Remote Display(s)
Configure Home Screen Display