FCS - Operation Manual
`
When the preconfigured silenced amount of time (OFF Delay) has passed, the strobe/horn
and buzzer will sound and the Silence? screen will appear again. The silence interval is
specific to each audible relay. The OFF Delay for that relay sets the silence duration.
To let the alarm(s) continue sounding, don’t press Silence All. Each alarm will continue
sounding until the cause of the alarm comes to an end.
NOTE:
The Silencing functionality applies to ALL relays that have been configured as
silenceable. However, it is intended for AUDIBLE devices (horns, integral buzzer, etc.) directly
connected to the FCS or the relays (including the RLY-4 or RLY-8); but any relay can be
configured as silenceable.
5 TESTING FUNCTIONS
In the Test menu, you can test the audible alarm, strobe and relays and analog output to
ensure they are working correctly. For each test you can set the length of time for the test to
last.
Press Menu and enter passcode “1” to enter the Test Menu.
The maximum length of time each test can be set to last is 1 hour. The range that can be set
is 0 seconds to 60 minutes.
When the test starts, it will continue as long as the time was set. You can exit the Test menu
without affecting the time. If you want to end the test before the time is up, you must re-enter
the Test menu and enter a value of “0” for the test length of that function.