Connect on/off thermostat
Tk
ON/OFF room thermostat
The boiler is suitable for connection to a 2 wire on/off room thermostat.
4
Install the regulator in the reference room (generally the living
room).
4
Connect the 2 wire 24V room thermostat to the
On/off-OT
terminals of the connector.
4
Connect the power stealing thermostat to the
On/off-OT
terminals
of the connector.
If a room thermostat with an anticipation element is used,
this must be converted using parameter
p5
.
4.8.6.
Connecting the outside temperature
sensor
Ba
Outside sensor
An outside sensor can be connected to the
Tout
terminals of the
connector. Where there is an on/off thermostat controller, the boiler
will control the temperature with the set point of the internal heating
curve.
A OpenTherm controller can also use this outside sensor.
The heating curve required must then be set on the
controller.
n
Heating curve setting
If an outside temperature sensor is connected, it is possible to adapt
the heating curve. The setting can be modified using parameters
p1
,
p"5
,
p"6
and
p"7
.
T001590-B