4.7.3.
Lengths of the air/flue gas pipes
4
The boiler is also suitable for longer chimney lengths
with diameters other than those indicated in the
table. Please contact us for further information.
4
To define the maximum final length, you must deduct
the pipe length in accordance with the reduction table.
n
Open flue (B23, B23P, B33)
If using an open flue version, the air supply opening remains open;
only the combustion gas opening is connected. The boiler then takes
in the combustion air required directly from the premises in which it
is installed.
CAUTION
4
The air supply opening must remain open.
4
The premises in which the appliance is installed must
be fitted with the necessary air supply openings.
They must not be reduced or closed.
Chimney length for the open flue version
Diameter
Maximum length (
L
)
Quinta Pro
30
45
65
90
115
80 mm 40 m 33 m 10 m 9 m
8 m
90 mm 40 m 40 m 18 m 16 m 12 m
100 mm 40 m 40 m 27 m 24 m 19 m
110 mm 40 m 40 m 40 m 40 m 37 m
n
Room sealed flue (C13, C33, C43, C63, C93)
If using a room sealed version, both the combustion gas exhaust
opening and the air supply opening must be connected
(concentrically). Refer to the table to determine the maximum pipe
length of the flue gas pipes in room sealed operation.
Chimney length for room sealed operation
Diameter
Maximum length (
L
)
Quinta Pro
30
45
65
90
115
80-125 mm 20 m 16 m
-
-
-
100-150 mm 20 m 20 m 13 m 13 m 7 m
T002998-A
T001882-B
L
4. Installation
Quinta Pro 30 - 45 - 65 - 90 - 115