4. Connect the pump connection cable to the cable bundle by
opening and closing the cable bundle bands.
4.8.5.
Connecting a third party control unit
n
Connecting modulating controller
OT
OpenTherm
regulator
The boiler is fitted with a
OpenTherm
connection as standard.
As a result, modulating
OpenTherm
controllers can be connected
without further modifications (Room, weather-dependent and
cascade controllers). The boiler is also suitable for
OpenTherm
Smart Power
.
4
In the case of a room controller: Install the regulator in the
reference room (generally the living room).
4
Connect the two-wire cable to terminals
On/off-OT
of the
connector.
If the tap water temperature can be set on the
OpenTherm
controller, then the boiler supplies this
temperature, with the set value on the boiler as the
maximum.
T002049-B
T000776-D
On/off
OT
BL
RL
Tout
Tdhw
OT
On/off
Tou
t
Tdhw
BL
RL
OT
4. Installation
Quinta Pro 30 - 45 - 65 - 90 - 115
30
250413 - 123157-03