3.4
Technical specifications
Boiler type
Quinta Pro
30
45
65
90
115
General
EC indentification no.
PIN
0063CL3333
Gas Council number
41-288-15 41-288-16 41-288-17
Flow rate setting
Adjustable
Modulating, Start/Stop, 0 - 10 V
Nominal output (Pn)
Heating System (80/60 °C)
minimum-
maximum
kW
8.0 - 29.3 8.0 - 40.0 12.0 - 61.0 14.1 - 84.2 16.6 - 107.0
Factory setting
kW
29.3
40.0
61.0
84.2
107.0
Nominal output (Pn)
Heating System (50/30 °C)
minimum-
maximum
kW
8.9 - 31.4 8.9 - 43.0 13.3 - 65.0 15.8 - 89.5 18.4 - 114.0
Factory setting
kW
31.4
43.0
65.0
89.5
114.0
Nominal input (Qn)
Heating System (Hi)
minimum-
maximum
kW
8.2 - 30.0 8.2 - 41.2 12.2 - 62.0 14.6 - 86.0 17.2 - 110.2
Factory setting
kW
30.0
41.2
62.0
86.0
110,2
Nominal input(Qn)
Heating System (Hs)
minimum-
maximum
kW
9.1 - 33.3 9.1 - 45.7 13.6 - 68.8 16.2 - 95.5 19.1 - 122.4
Factory setting
kW
33.3
45.7
68.8
95.5
122.4
Heating efficiency under full load
(Hi) (80/60 °C)
-
%
97.5
97.2
98.3
97.9
96.6
Heating efficiency under full load
(Hi) (50/30 °C)
-
%
102.9
102.9
104.6
104.1
102.5
Heating efficiency under partial
load (Hi) (Return temperature
60°C)
-
%
97.5
97.5
98.3
96.6
96.5
Heating efficiency under partial
load (EN 92/42)(Return
temperature 30°C)
-
%
107.7
107.7
108.9
108.1
107.1
Data on the gases and combustion gases
Gas categories
-
II
2H3P
Gas inlet pressure at boiler
connection - G20 (Gas H)
minimum-
maximum
mbar
17- 30
Gas inlet pressure at boiler
connection - G31 (Propane)
minimum-
maximum
mbar
37 - 50
Gas resistance between boiler
connection and measurement
point on the gas valve unit
mbar
1
1
2
2.5
3
Gas consumption - G20 (Gas H) minimum-
maximum
m
3
/h
0.9 - 3.3
0.9 - 4.4
1.3 - 6.6
1.5 - 9.1
1.8 - 11.7
Gas consumption - G31
(Propane)
minimum-
maximum
m
3
/h
0.3 - 1.3
0.3 - 1.7
0.5 - 2.5
0.6 - 3.5
0.6 - 4.7
NOx-Emission per year
(BREEAM)
mg/kWh
37
37
32
29
35
Mass flue gas flow rate
minimum-
maximum
kg/h
14 - 50
14 - 69
21 - 104
28 - 138
36 - 178
Flue gas temperature
minimum-
maximum
°C
30- 65
30 - 67
30 - 68
30 - 68
30 - 72
Maximum counter pressure
Pa
70
150
100
160
220
Characteristics of the heating circuit
Water content
l
5.5
5.5
6.5
7.5
7.5
Water operating pressure
minimum
bar
0,8
(1) Front panel removed
Quinta Pro 30 - 45 - 65 - 90 - 115
3. Technical description
250413 - 123157-03
13