4
For long, aluminium, combustion-gas exhaust pipes it is initially
necessary to consider the relatively high quantity of corrosive
products which are brought together with the condensate from the
exhaust pipe. The siphon on the equipment requires regular
cleaning or, preferably, an additional condensate collector can be
installed above the equipment.
4
The combusted gas discharge pipe must be sufficiently inclined
towards the boiler (at least 50 mm per metre) and an adequate
condensate collection tank and discharge system constructed (at
least 1 m before the boiler opening). The elbows fitted must be at
more than 90° to guarantee the provision of an adequate gradient
and tightness on the lip rings.
Please contact us for further information.
4.7.5.
Connection of the combustion gas exhaust
pipe
S
Insertion depth 25 mm
Mounting
Fit together the combustion gas exhaust pipes, without welding.
4
The pipes must allow no leakage of flue gases and be
resistant to corrosion.
4
Connect the pipes together without stress between
the sections.
4
The horizontal sections need to be constructed with a
gradient of 50 mm per metre: Boiler orientation.
4.8
Electrical connections
4.8.1.
Control unit
The boiler is not line- and neutral sensitive. The boiler is fully pre-
wired. All external connections can be made on the connection
connector (low voltage). The main characteristics of the control unit
are described in the table below.
Power supply voltage
230 VAC/50Hz
Rating of the main fuse F1 (230 VAC) 6.3 AT
Fuse rating F2 (230 VAC)
2 AT
Fan
230 VAC
T001990-A
80/125 mm
100/150 mm
S
4. Installation
Quinta Pro 30 - 45 - 65 - 90 - 115
26
250413 - 123157-03