5.7
Changing the settings
The boiler control panel is set for the most common heating
systems. With these settings, practically all heating systems operate
correctly. The user or installer can optimise the parameters according
to own preferences.
For operation in open vented systems, several parameter settings
must be adjusted. Set the various parameters according to the values
given in the table below.
5.7.1.
Parameter descriptions
Parameter
Description
Adjustment range
Factory setting
Quinta Pro
30 45 65 90 115
p1
Flow temperature: T
SET
20 to 90 °C
80
p1
Open vented:
Flow temperature: T
SET
20 to 90 °C
75
p2
Domestic hot water
temperature: T
SET
40 to 65 °C
55
p3
Heating / DHW mode
0 = Heating deactivated / DHW deactivated
1 = Heating activated / DHW activated
2 = Heating activated / DHW deactivated
3 = Heating deactivated / DHW activated
1
p4
ECO mode
0 = Comfort
1 = Energy-saving mode
2 = Management using a programmable thermostat
2
p5
Anticipation resistance
0 = No anticipation resistance for the ON/OFF
thermostat
1 = Anticipation resistance for the ON/OFF
thermostat
0
p6
Display screen
0 = Simple
1 = Comprehensive
2 = Automatic switching to simple after 3 minutes
3 = Automatic switching to simple after 3 minutes;
Key blocking is active
2
p7
Post-circulation of the pump
1 to 98 minutes
99 minutes = continuous
3
p8
Brightness of display lighting
0 = Dimmed
1 = Bright
1
(1) Do not modify these factory settings unless absolutely necessary. E.g. to adapt the boiler to: (Propane)
(2) If the unit is being installed in a cascade system, set parameter
47
to 20
Quinta Pro 30 - 45 - 65 - 90 - 115
5. Commissioning
250413 - 123157-03
55