7. The start-up cycle begins and cannot be interrupted. During the
start-up cycle, the display shows the following information:
A short test where all segments of the display are visible.
fK[xx
: Software version
pK[xx
: Parameter version
The version numbers are displayed alternately.
8. A vent cycle of a duration of around 3 minutes is carried out
automatically.
If a DHW sensor is connected and the anti-legionella
function is activated, the boiler starts to heat the water in
the DHW tank as soon as the vent programme has been
completed.
By pressing the
®
key for a short time, the current operating status
is shown on the display:
Heat demand
5D
Heat demand stopped
1
: Fan ON
1
: Post-ventilation
"
: Boiler is igniting
5
: Burner stop
6
: Post-circulation of the pump
3
: Heating System
0
: Standby
In addition to
0
, in STAND-BY the display normally shows the water
pressure and the symbols
5D
,
5H
and
N
.
Error during the start-up procedure:
4
No information is shown on the display:
-
Check the mains supply voltage
-
Check the main fuses
-
Check the fuses on the control panel:
(F1 = 6.3AT, F2 = 2 AT)
-
Check the connection of the mains lead to the connector
X1
in
the instrument box
4
A fault is indicated on the display by the fault symbol
c
and a
flashing fault code.
-
The meaning of the error codes is given in the error table.
-
Press for 3 seconds on key
J
to restart the boiler.
If the economy setting (eco setting) is on, then, after central
heating operation, the boiler will not start to run for hot tap
water production.