Applications manual
For AME series
6.9.5
READ_WRITE_PROTECT_PRM [1Eh] [09h] [15h] [00h]
This command returns the status of WRITE PROTECTION.
Return value:0
=>
WRITE PROTECTION is disabled.
Return value:1
=>
WRITE PROTECTION is enabled.
*
*Error code 224 : The specified command is not valid
.
6.9.6
SYS_STORE_USER_SETTING [1Eh] [09h] [00h] [10h]
XX = ON or OFF.
5
Send
"
SET_WRITE_PROTECT_OFF
"
0
OFF
6
Send
"
CTL_REMOTE_ON
"
1
ON
SET_SELECTION_CH
Setting target
SYS_STORE_USER_SETTING Supported commands
Input module
(Set value: 0)
CTL_REMOTE_XX
:Output ON / OFF setting status by communication
CTL_CH_REMOTE_XX
:Output ON / OFF setting status by communication
CTL_REMOTE_XX_CH
:Output ON / OFF setting status by communication
CTL_POWER_XX_GI
:Global inhibit setting by communication
SET_GI_TERMINAL_MODE_GI
:GI terminal setting mode
SET_GI_TERMINAL_MODE_RC
:GI terminal setting mode
3
Send
"
SET_WRITE_PROTECT_ON
"
1
OFF
4
Send
"
CTL_REMOTE_ON
"
224
OFF
1
Power-on
-
ON
2
Send "
CTL_REMOTE_OFF
"
0
OFF
Operation
Return value
AME Output
Table 6.9.1
"SET_WRITE_PROTECT_ON" Operation example
(
AME series
)
Status
SET_TON_DELAY_SLOT
:Delay time from the output voltage is turned on
SET_TOFF_DELAY_SLOT
:Delay time from the output voltage is turned off
SET_TON_DELAY_VIN
:Delay time from input
SET_START_UP_VIN_AC
:start-up input voltage (AC)
SET_STOP_VIN_AC
:stop input voltage (AC)
SET_FAN_MODE_AUTO
:Rotational speed control mode of air cooling fan
SET_FAN_MODE_FIXED_SPEED
:Rotational speed control mode of air cooling fan
SET_AUX_VOUT
:AUX output voltage setting
SET_VIN_LV_ALARM
:Input voltage to output alarm signal
SET_PR_TERMINAL_MODE_PR
:PR terminal setting mode
SET_PR_TERMINAL_MODE_PG
:PR terminal setting mode
SET_ALARM_STATUS
Setting of abnormal condition to output alarm signal
SET_WRITE_PROTECT_XX
:the current write-protection mode
CTL_ACCUMULATE_MODE_XX
:setting status of the accumulate mode
SET_ADDRESS
:setting the communication address
Stored values and settings can remain even during power-off.
This command stores settings of target module selected by "SET_SELECTION_CH" command in
non-volatile memory of each module.
This command needs to be executed to every target module individually.
Commands corresponding to this command are shown below.
This command stores value and/or settings set by the communication function in the
non-volatile memory of the AME.
43
ver1.1E 2020.2.12