Applications manual
For AME series
6.5.9
SET_START_UP_VIN_AC [17h] [00h] [
Argument
]
80 - 240VAC
Argument:170 => 170VAC
Argument value
6.5.10
READ_START_UP_VIN_AC_PRM [1Eh] [09h] [1Ch] [00h]
This command returns the value (argument value) set by "SET_START_UP_VIN_AC" command.
6.5.11
SET_STOP_VIN_AC [17h] [01h] [
Argument
]
75 - 150VAC
argument:90 => 90VAC
argument value
6.5.12
READ_STOP_VIN_AC_PRM [1Eh] [09h] [1Ch] [01h]
This command returns the value (argument value) set by "SET_STOP_VIN_AC" command.
When the input voltage is 90VAC or less, load derating is required. Refer the AME series
instruction manual for the detail.
Return value
This command sets the starting voltage for the AC input.
Store the setting value by "SYS_STORE_USER_SETTING" command after this command is
transmitted. Then, wait for 30 seconds or more after power-off. The setting will get enabled from
next start-up.
With this command, the starting voltage cannot be set to the value which is lower than 5V higher
value than the one by "SET_STOP_VIN_AC" command. If specified, this command is not accepted
and an error is returned. (Error code 1 : The argument outside settable range is specified.)
Settable range
Example of argument
Return value
When the input voltage is 90VAC or less, load derating is required. Refer the AME series
instruction manual for the detail.
This command sets the stopping voltage for the AC input.
Store the setting value by "SYS_STORE_USER_SETTING" command after this command is
transmitted. Then, wait for 30 seconds or more after power-off. The setting will get enabled from
next start-up.
With this command, the starting voltage cannot be set to the value which is higher than 5V lower
value than the one by "SET_START_UP_VIN_AC" command. If specified, this command is not
accepted and an error is returned. (Error code 1 : The argument outside settable range is specified.)
Settable range
Example of argument
29
ver1.1E 2020.2.12