6.7 Monitor commands
6.7.1
MON_VIN [1Eh] [08h] [00h] [01h]
6.7.2
MON_VIN_FREQUENCY [1Eh] [08h] [00h] [1Fh]
6.7.3
MON_VOUT [1Eh] [08h] [01h] [00h]
If the front-end module is targeted, an error is returned.
(Error code 6 : Command that do not correspond to the setting target)
6.7.4
MON_IOUT [1Eh] [08h] [05h] [00h]
If the front-end module is targeted, an error is returned.
(Error code 6 : Command that do not correspond to the setting target)
6.7.5
MON_OUTPUT_POWER [1Eh] [08h] [08h] [10h]
If the front-end module is targeted, an error is returned.
(Error code 6 : Command that do not correspond to the setting target)
This command returns the RMS value of the input voltage. It discriminates DC from AC
automatically.
The input voltage, in V, is the value of "Return value /100".
If the input voltage was distorted, the return value may not be correct.
Example of return value
Example of return value
Return value:24010 => AC240.10V
This command returns the frequency of the input voltage.
The frequency, in Hz, of the input voltage is the value of "Returned value / 10". When the input is
"DC", the return value is "0".
It will be unsettled for five seconds from power-on.
Return value:481 => 48.1Hz
This command returns the output voltage (voltage between the sensing terminals).
The output voltage, in V, is the value of "Returned value / 1000".
Example of return value
Return value:24200 => 24.200V
If the instruction is executed on an output module other than the corresponding output modules, an
error is returned.(Error code 6 : Command that do not correspond to the setting target)
This command returns the output current.
The output current, in A, is the value of "Returned value / 100".
Example of return value
Return value:1350 => 13.50A
If the instruction is executed on an output module other than the corresponding output modules, an
error is returned.(Error code 6 : Command that do not correspond to the setting target)
This command returns the output power.
The output power, in W, is the value of "Returned value / 10".
Example of return value
Return value:6000 => 600.0W
If the instruction is executed on an output module other than the corresponding output modules, an
error is returned.(Error code 6 : Command that do not correspond to the setting target)
Applications manual
For AME series