Applications manual
For AME series
6.6.6
SET_VIN_LV_ALARM [16h] [18h] [
Argument
]
75 - 240V
Argument:95 => 95V
Argument value
6.6.7
READ_VIN_LV_ALARM_PRM [1Eh] [09h] [1Eh] [03h]
This command returns the value (argument value) set by "SET_VIN_LV_ALARM" command.
6.6.8
SET_PR_TERMINAL_MODE_PR [1Eh] [09h] [0Eh] [08h]
This command sets the PR terminal to work for the abnormal detection (PR alarm function).
This is the factory default.
6.6.9
SET_PR_TERMINAL_MODE_PG [1Eh] [09h] [0Eh] [09h]
6.6.10
READ_PR_TERMINAL_MODE_PRM [1Eh] [09h] [1Eh] [0Dh]
This command returns a status of the detection function in the PR terminal.
Return value:0
=>
PR alarm function
Return value:1
=>
PG alarm function
6.6.11
SET_ALARM_STATUS [16h] [19h] [Argument]
The relationship between the argument (binary) and abnormal conditions is shown below.
The factory default of the argument is "00011b" (Abnormal input voltage and fan stoppage).
This command setting the PR terminal to work for the detection of the front-end module stoppage (PG
alarm function).
This command sets the abnormal conditions in which an alarm signal is output from the PR terminal,
by the argument.
Return value
1
Status
This command sets the input threshold voltage for the alarm signal from PR terminal.
It sets the argument to the input voltage, in V, for the alarm signal which detects lower input voltage.
Settable range
Example of argument
Return value
Return value
0
3bit
:
Overpower protection in front-end
module activated.
4bit
:
Thermal protection in output module
activated.
0bit
︓
Abnormal input voltage (low input
voltage).
1bit
︓
Fan stopped.
2bit
:
Thermal protection in front-end module
activated.
1
1
1
b
Argument (binary )
1
1
33
ver1.1E 2020.2.12