Appendix C -
Expansion I/O Registers
Adding 115S Expansion I/O modules to the 450U-E the I/O will automatically be added to the 450U-E modules I/O store.
To calculate the register location, add the address of the I/O point from the tables below to the offset.
The offset ids calculated by finding the address of the Modbus Slave X 20.
E.g1. Digital input #1 on an 115S-11 with address 5 would be: (5x20) +10001 = 10101
E.g2. Digital output #2 on an 115S-11 with address 6 would be: (6x20) +2 = 122
E.g3. Analog input #3 on an 115S-12 with address 3 would be: (3x20) +30003 = 30063.
E.g4. Analog Output #8 on an 115S-13 with address # 7 would be: (7x20) + 40007 = 40147
I/O store for a 115S-11 Expansion I/O module
I/O store for a 115S-12 Expansion I/O module
0001 - 0008 + Offset
DIO Outputs 1 - 8
10001 - 10008 + Offset
DIO Inputs 1 - 8
10019 + Offset
Modbus Error indication for 115S module
10020 + Offset
Detected indication for this 115S module
30001 - 30008 + Offset
Inputs AIN 1 AIN8
30017 + Offset
Modbus Error Counter for this 115S module
30018 + Offset
Modbus Last Error Code for this 115S module. (Appendix D - Modbus Error
Codes)
30019 + Offset
Modbus Lost Link Counter for this 115S module
30020 + Offset
Module type (0x0201) = 513. / Error Status
40009 - 40016 + Offset
Pulsed Output target 1 8 (1 register per output)
I/O store for a 115S-13 Expansion I/O module
0001 - 0008 + Offset
DIO Outputs 1 - 8
10001 - 10008 + Offset
DIO Inputs 1 - 8
10019 + Offset
Modbus Error indication for 115S module
0001 - 0016 + Offset
DIO Outputs 1 - 16
10001 -10016 + Offset
DIO Inputs 1 - 16
10019 + Offset
Modbus Comms Fail indication for this 115S module
10020 + Offset
Modbus Comms Fail indication (Inverse) for this 115S module
30001 -30004 + Offset
115S-11 pulsed input rate 1 4
30005 - 30012 + Offset
115S-11 Pulsed input count
30017 + Offset
Modbus Error Counter for this 115S module
30018 + Offset
Modbus Last Error Code for this 115S module. (Appendix D - Modbus Error
Codes)
30019 + Offset
Modbus Lost Link Counter for this 115S module
30020 + Offset
Module type (0x0101) = 257. / Error Status
40009 - 40016 + Offset
Pulsed Output target 1 8 (1 register per pulsed output)