All registers within the module can have various states depending on what type of register it is and what sort of value it
holds, a typical analog range is between 0 and 65535 and a digital can be 0 or 1.
Registers can also have
so does not hold a value but more a non-value or null.
as a
shown above.
Any mapping with an invalid register will be inhibited from sending. This is to ensure the data that
gets to the destination is valid and not just default values that the module starts up with.
Configuration Examples
3.17
Extending a wired network (Bridged Network)
Access Point Configuration
Connect straight through Ethernet cable between PC and 450U-E.
Ensure configuration PC and 450U-E are setup to communicate on the same network
Set dipswitch to SETUP mode.
Power up unit, and wait for the OK LED to cease flashing.
Adjust PC network settings
Set Configuration PC network card with network setting of IP address 192.168.0.1, Netmask 255.255.255.0
Open configuration webpage with Internet Explorer at address 192.168.0.1XX/ where XX is the last two digits of the
serial number
screen.
On this screen select the Transmit Power level, Transmit Data Rate, Frequency Step size and Transmit & Receive
Frequencies
Select Operating Mode as Access Point.
Figure 59 - Example Config 1
Figure 58 - Invalid Register State