Web Server
XW-210 WiFi™ Users Manual
command is sent to the remote device to pulse the relay.
If
Relay
is selected the following Action options are available:
Remote command equals relay:
When the local relay is on, a command is sent to the remote
device to set the relay state to
on
. When the local relay is off, a command is sent to the remote
device to set the relay state to
off
.
Remote command opposite of relay:
When the local relay is on, a command is sent to the remote
device to set the relay state to
off
. When the local relay is off, a command is sent to the remote
device to set the relay state to
on
.
Send on command when relay [on, off, changes] (no off command):
When the local relay is [on,
off, changes], a command is sent to the remote device to set the relay state to
on
. No off commands
are sent to the remote device..
Send off command when relay [on, off, changes] (no on command):
When the local relay is [on,
off, changes] a command is sent to the remote device to set the relay state to
off
. No on commands
are sent to the remote device.
Send toggle command when relay [on, off, changes]:
When the local relay is [on, off, changes] a
command is sent to the remote device to toggle the relay (change the remote relay to the state
opposite of its current state).
Send pulse command when relay [on, off, changes]:
When the local relay is [on, off, changes] a
command is sent to the remote device to pulse the relay.
If
1-Wire Sensor
is selected, choose the sensor number. For each sensor the following action options are
available:
Send On Command When [Alarm1, Alarm2, Alarm1 or Alarm2]:
A command is sent to the remote
device to set the relay state to on when [Alarm1, Alarm2, Alarm1 or Alarm2] becomes true. A
command is sent to the remote device to set the relay state to off when [Alarm1, Alarm2, Alarm1 or
Alarm2] becomes false.
Send Off Command When [Alarm1, Alarm2, Alarm1 or Alarm2]:
A command is sent to the remote
device to set the relay state to off when [Alarm1, Alarm2, Alarm1 or Alarm2] becomes true. A
command is sent to the remote device to set the relay state to on when [Alarm1, Alarm2, Alarm1 or
Alarm2] becomes false.
Send On Command When [Alarm1, Alarm2, Alarm 1 or Alarm2] (no off command):
A command
is sent to the remote device to set the relay state to on when [Alarm1, Alarm2, Alarm1 or Alarm2]
becomes true. No off command is sent.
Send Off Command When [Alarm1, Alarm2, Alarm 1 or Alarm2] (no on command):
A command
is sent to the remote device to set the relay state to off when [Alarm1, Alarm2, Alarm1 or Alarm2]
becomes true. No on command is sent.
Send toggle command when [Alarm 1, Alarm2, Alarm 1 or Alarm2]:
A command is sent to the
remote device to toggle the relay (change the remote relay to the state opposite of its current state
when [Alarm1, Alarm 2, Alarm 1 or Alarm 2] becomes true.
Send Pulse Command When [Alarm1, Alarm2, Alarm1 or Alarm2]:
A command is sent to the
remote device to pulse the relay when [Alarm1, Alarm 2, Alarm 1 or Alarm 2] becomes true.
Page 46
Xytronix Research & Design, Inc.
Summary of Contents for WebRelay Wireless XW-210I
Page 1: ......