3.12.2 Terminal sizes and torque settings
Table 3-4 Drive control terminal data
Table 3-5 Drive power terminal data
Table 3-6 Size 5 fan supply connection
Table 3-7 RFI Filter terminal data
For all the RFI filters, except the size 5 (4200-6115), the power
connections are screw terminals and the ground connections are stud
terminals.
3.13 Routine maintenance
The drive should be installed in a cool, clean, well ventilated location.
Contact of moisture and dust with the drive should be prevented.
Regular checks of the following should be carried out to ensure drive /
installation reliability is maximised:
To avoid a fire hazard and maintain validity of the UL listing,
adhere to the specified tightening torques for the power and
ground terminals. Refer to the following tables.
Model
Connection type
Torque setting
All
Plug-in terminal block
0.5 N m 4.4 lb in
Model size
AC terminals
DC terminals
Ground terminal
1
Plug-in terminal block
0.5 N m / 4.4 lb in
M4 (Torx/slot-head screw)
3 N m / 2.2 lb ft
2
Plug-in terminal block
0.5 N m / 4.4 lb in
M4 (Torx/slot-head screw)
3 N m / 2.2 lb ft
3
M10 stud
15 N m / 11 lb ft
M10 stud
15 N m / 11 lb ft
4
M10 stud
15 N m / 11 lb ft
M10 stud
15 N m / 11 lb ft
5
M10 bolt & nut 25
N m / 22.1 lb ft
M10 hole
25 N m / 22.1 lb ft
M10 stud
25 N m / 22.1 lb ft
Torque tolerance
±
10%
Type
Torque setting
Terminal block M4 Pozidriv screw
0.5 N m 4.4 lb in
CT
part
number
Schaffner
part
number
Power
connections
Ground
connections
Max cable
size
Torque
Size
Torque
4200-6104
FS5101-10-07
4 mm
2
10 AWG
0.8 N m
7.1 lb in
M5
2.2 N m
19.5 lb in
4200-6105
FS5111-10-29
4 mm
2
10 AWG
0.8 N m
7.1 lb in
M5
2.2 N m
19.5 lb in
4200-6108
FS5106-16-07
4 mm
2
10 AWG
0.8 N m
7.1 lb in
M5
2.2 N m
19.5 lb in
4200-6109
FS5112-16-07
4 mm
2
10 AWG
0.8 N m
7.1 lb in
M5
2.2 N m
19.5 lb in
4200-6113
FS5106-25-07
4 mm
2
10 AWG
0.8 N m
7.1 lb in
M5
2.2 N m
19.5 lb in
4200-6114
FS5113-25-29
4 mm
2
10 AWG
0.8 N m
7.1 lb in
M5
2.2 N m
19.5 lb in
4200-6116
FS5113-50-53
10 mm
2
6 AWG
4.5 N m
3.3 lb ft
M5
2.2 N m
19.5 lb in
4200-6117
FS5113-63-34
10 mm
2
6 AWG
4.5 N m
3.3 lb ft
M6
4.0 N m
2.9 lb ft
4200-6106
FS5113-100-35
50 mm
2
1/0 AWG
8.0 N m
5.9 lb ft
M8
9.0 N m
6.6 lb ft
4200-6107
FS5113-150-40
95 mm
2
4/0 AWG
20.0 N m
14.7 lb ft
M10
18.0 N m
13.3 lb ft
4200-6111
FS5113-180-40
95 mm
2
4/0 AWG
20.0 N m
14.7 lb ft
M12
20.0 N m
14.7 lb ft
4200-6112
FS5113-220-37
150 mm
2
6/0 AWG
30.0 N m
22.1 lb ft
M12
20.0 N m
14.7 lb ft
4200-6115
FS5113-300-99
M12 stud
30.0 N m
22.1 lb ft
M12
stud
20.0 N m
14.7 lb ft
WARNING
Environment
Ambient temperature
Ensure the enclosure temperature remains at or below
40
°
C (50
°
C when derating applied)
Dust
Ensure the drive remains dust free – check that the
drive fan is not gathering dust. The lifetime of the fan is
reduced in dusty environments.
Moisture
Ensure the drive enclosure shows no signs of
condensation
Enclosure
Enclosure door filters
Ensure filters are not blocked and that air is free to
flow
Electrical
Screw connections
Ensure all screw terminals remain tight
Crimp terminals
Ensure all crimp terminals remains tight – check for
any discolouration which could indicate overheating
Cables
Check all cables for signs of damage