10.10 Menu 10: Status flags / trip log
Where a parameter is represented by a text value, the value in brackets
in the range column is the setting used for serial communications.
Parameter
Range(
Ú
)
Default(
Ö
)
Type
OL
CL
OL
VT
SV
10.01
Drive normal
indicator
0 or 1
RO Bit
P
10.02
Drive running
indicator
0 or 1
RO Bit
P
10.03
At zero speed
indicator
0 or 1
RO Bit
P
10.04
At or below min. speed
indicator
0 or 1
RO Bit
P
10.05
Below at-speed window
indicator
0 or 1
RO Bit
P
10.06
At speed
indicator
0 or 1
RO Bit
P
10.07
Above at-speed window
indicator
0 or 1
RO Bit
P
10.08
At 100% load
indicator
0 or 1
RO Bit
P
10.09
Current-limit active
indicator
0 or 1
RO Bit
P
10.10
Motor regenerating
indicator
0 or 1
RO Bit
P
10.11
Dynamic brake active
indicator
0 or 1
RO Bit
P
10.12
Dynamic brake alarm
indicator
0 or 1
RO Bit
P
10.13
Direction demanded
indicator
0 or 1
RO Bit
P
10.14
Direction running
indicator
0 or 1
RO Bit
P
10.15
AC
supply loss
indicator
0 or 1
RO Bit
P
10.16
Motor thermistor over-temperature
indicator
0 or 1
RO Bit
P
10.17
Motor current overload alarm
indicator
0 or 1
RO Bit
P
10.18
Heatsink temperature alarm
indicator
0 or 1
RO Bit
P
10.19
Ambient temperature alarm
indicator
0 or 1
RO Bit
P
10.20
Last trip
0 to 200
RO Txt S
P
10.21
Second last trip
0 to 200
RO Txt S
P
10.22
Third last trip
0 to 200
RO Txt S
P
10.23
Fourth last trip
0 to 200
RO Txt S
P
10.24
Fifth last trip
0 to 200
RO Txt S
P
10.25
Sixth last trip
0 to 200
RO Txt S
P
10.26
Seventh last trip
0 to 200
RO Txt S
P
10.27
Eighth last trip
0 to 200
RO Txt S
P
10.28
Ninth last trip
0 to 200
RO Txt S
P
10.29
Tenth last trip
0 to 200
RO Txt S
P
10.30
Max. full-power braking time
0 to 400.0 s
0
RW Uni
10.31
Max. full-power braking interval
0 to 25.0 min
0
RW Uni
10.32
External trip active
indicator
0 or 1
RO Bit
10.33
Drive reset
0 or 1
0
RW Bit
10.34
Number of auto- reset attempts
0 to 5
0
RW Uni
10.35
Auto-reset time delay
0 to 25.0 s
1.0
RW Uni
10.36
Hold drive healthy until last auto-reset
attempt
select
0 or 1
0
RW Bit
10.37
Stop drive on non-important trips
0 or 1
0
RW Bit
10.38
User trip
0 to 200
0
RW Uni
P
10.39
Braking-energy overload accumulator
0 to 100.0 %
RO Uni
P
10.40
Status word
0 to 32,767
RO Uni
P
10.41
UD78 auxiliary power supply active
indicator
0 or 1
RO Bit
P
10.42
IGBT junction temperature above 135
o
C
indicator
0 or 1
RO Bit
P
RO
Read Only parameter
Uni
Unipolar variable parameter
R
Reset required for new value to take effect
Bi
Bipolar variable parameter
S
New parameter-value saved at power-down
RW
Read / Write parameter
Txt
Text variable parameter
P
Protected; forbidden as destination parameter
Bit
Bit parameter
FLC
Full-load current (max. continuous), Pr
11.32
{
0.33
}
NOTE