 III) LOCATION & MOUNTING  

The P2621-NO2/VC can be used to monitor up to 10,000 square feet of undivided area.  
It can be used as a self-contained, stand-alone control or as part of a multi sensor Control 
system.  If the airflow is not uniform or if the area to be monitored is unusual, then the 
area by each unit should be appropriately reduced.  

Select an appropriate mounting location in an area of heavy traffic flow, away from drafts 
and where the vent holes on the bottom of the unit will not be blocked.  Mount the unit 
with four (4) screws using the external mounting feet provided.  The unit should be at a 
convenient height, typically five (5) feet above the floor.  

IV) INSTALLATION & WIRING  

After mounting the unit(s) as described above, connect the power and relay wires as 
shown in INSTALLATION DIAGRAM page 9 of this manual.  The power circuit and 
Control circuit of the unit(s) must be wired with 18 AWG or heavier copper wire.  A 
multiple sensor installation requires only a simple series Connection of the fan Control 
relays.  This feature allows for maximum flexibility in system design and installation.  
Zoned systems are easily created when several sets of fans need to be controlled 
independently.  

1. 

Be sure to turn OFF power to fan Control system and 24 VAC power supply 
before wiring and Connections are made.  

2. 

Open the enclosure using the provided hex-key.  The Control card is mounted on 
the inside of the enclosure door.  A terminal block for electrical Connections is 
located on the back panel of the monitor.  The terminals are marked for power 
input and relay Connections.  

3. 

The wiring must enter the P2621-NO2/VC enclosure through the two (2) 
electrical openings provided on the unit with conduit fittings.  

4. 

Connect 24 VAC power supply to terminals T1 and T2 of the terminal block.  
Each P2621 unit requires 12 watts of power for proper operation.  

5. 

Connect the relay (Control) Contacts K1 and K2 in series with the coil of the 
ventilation fan control, intermediate relay, or K1 and K2 of the next unit (for 
multiple units configuration).  NOTE: the P2621-NO2/VC must be wired so 
that the fans are ON when the relay contacts K1 and K2 are open.
  

6. 

OPTIONAL ALARM RELAY- Connect the optional relay (alarm relay) Contacts 
K3 and K4, if so equipped, as shown in Installation Diagram page 9 of this 
manual.  

7. 

Verify that the wiring to each unit is correct. 

Summary of Contents for P2621-NO2/VC

Page 1: ...Conspec Controls Inc P2621 NO2 VC Nitrogen Dioxide Ventilation Fan Controller Operations Manual Conspec Controls Inc 1 800 487 8450...

Page 2: ...the relay coil is energized whenever the P2621 NO2 VC is in a non alarm condition and the normally open contact terminal connections K1 K2 is held closed When any fault occurs the Fan relay is de ene...

Page 3: ...ystem design and installation Zoned systems are easily created when several sets of fans need to be controlled independently 1 Be sure to turn OFF power to fan Control system and 24 VAC power supply b...

Page 4: ...t a regular interval Conspec stipulates a gas injection into the sensor and verify the response of the sensor for every THREE MONTHS of operation To perform an actual gas verification simply inject a...

Page 5: ...g three door retaining screws Open the door of the P2621 NO2 VC and locate the 20 header pin Connector marked J2 in the middle of the left edge of the P2065 Smart Monitor Card Plug the P2621 P program...

Page 6: ...sensor Press Key 4 once to accept the ZERO GAS calibration If the reading on LCD is outside the range of 25 100 the monitor should be sent back to the factory for in house calibration The message SCAL...

Page 7: ...ector on the P2065 Smart Monitor Card Clip the wire tie securing the cable to the lower left hand corner of the P2065 Smart Monitor Card and discard Grasp the ring protruding from the bottom of the P2...

Page 8: ...should be closed low or zero resistance If the circuit is not closed return the P2621 NO2 VC to your supplier or CONSPEC for repair or replacement If the above resistance checks between terminals K1 a...

Page 9: ...A Current Source Control Outputs Optional Strobe TB1 V Strobe P2065 J3 OUT 4 First Alarm Piezo TB1 V Piezo P2065 J3 OUT 3 Second Alarm NOTE The Control Outputs are open collector transistors limited t...

Reviews: