the power light is off, return the P2621-NO2/VC to your supplier or CONSPEC factory 
for repair or rep1acement.  

2. The Fan Does Not Operate When Fan Light (yellow light) is ON or

 

The Fan Does Not Turn OFF When The Fan Light (yellow light) is OFF

 

Turn OFF the power to the P2621 and to the fan Control system. Check that the field 
installed relay in the fan motor circuit is a (NC~ Normally Closed type.) Open the 
enclosure and check that the ventilation fan wiring is securely attached to the terminals 
K1 and K2, and that the wiring from the Connector terminals to the circuit board is 
securely attached. Disconnect the ventilation fan wiring from terminals K1 and K2. Using 
an ohmmeter, measure the resistance between terminals K1 and K2. The circuit should be 
open (high resistance). If the circuit is not open, return the P2621 to your supplier or 
CONSPEC for repair or replacement. Turn on the 24 VAC power to the P2621-NO2/VC 
and wait for -FAN- to appear in the display using an ohmmeter, measure the resistance 
between terminals K1 and K2. The circuit should be open (high resistance). If the circuit 
is not open, return the P2621 to your supplier or to CONSPEC for repair or replacement. 
With the 24VAC power to the P2621-NO2/VC turned OFF, wait for - FAN- to disappear 
from the display. Using an ohmmeter, measure the resistance between terminals K1 and 
K2.  The circuit should be closed (low or zero resistance). If the circuit is not closed, 
return the P2621-NO2/VC to your supplier or CONSPEC for repair or replacement. If the 
above resistance checks between terminals K1 and K2 are fine, turn OFF the 24 VAC 
power to the P2621-NO2/VC and reconnect the fan Control wiring. Turn ON the 24 VAC 
power to the unit and fan Control system. Check the fan operation. If the fan does not 
operate properly the problem is in the ventilation fan Control system or the Connecting 
wiring.  

3.  Fault Light Is ON

 

Turn OFF the 24 VAC power to the P2621-NO2/VC then turn it ON. If power cycling 
does not remove the fault condition turn OFF the 24 VAC power and power to the 
ventilation fan Control system. Open the enclosure and check that the connector from the 
sensor is attached to the main board. Turn ON the 24 VAC power to the P2621-NO2/VC. 
If the above steps do not remove the fault condition, turn OFF the 24 VAC power to the 
P2621-NO2/VC and return the unit to your supplier or Conspec for repair or replacement. 
The sensor is factory calibrated and the P2621-NO2/VC is ready to install and use. An 
optional field calibration kit is available when local regulations require periodic 
calibration checks of the sensor. When the sensor is about to fail, the red fail LED will 
light intermittently and will light steadily when the sensor fails. If the sensor is not 
replaced the P2621 will turn on the fans and go into the fail mode. The plug-in sensor 
module must be replaced before the unit can be reset.    

Conspec Technical Services: 724-489-8450     

Summary of Contents for P2621-NO2/VC

Page 1: ...Conspec Controls Inc P2621 NO2 VC Nitrogen Dioxide Ventilation Fan Controller Operations Manual Conspec Controls Inc 1 800 487 8450...

Page 2: ...the relay coil is energized whenever the P2621 NO2 VC is in a non alarm condition and the normally open contact terminal connections K1 K2 is held closed When any fault occurs the Fan relay is de ene...

Page 3: ...ystem design and installation Zoned systems are easily created when several sets of fans need to be controlled independently 1 Be sure to turn OFF power to fan Control system and 24 VAC power supply b...

Page 4: ...t a regular interval Conspec stipulates a gas injection into the sensor and verify the response of the sensor for every THREE MONTHS of operation To perform an actual gas verification simply inject a...

Page 5: ...g three door retaining screws Open the door of the P2621 NO2 VC and locate the 20 header pin Connector marked J2 in the middle of the left edge of the P2065 Smart Monitor Card Plug the P2621 P program...

Page 6: ...sensor Press Key 4 once to accept the ZERO GAS calibration If the reading on LCD is outside the range of 25 100 the monitor should be sent back to the factory for in house calibration The message SCAL...

Page 7: ...ector on the P2065 Smart Monitor Card Clip the wire tie securing the cable to the lower left hand corner of the P2065 Smart Monitor Card and discard Grasp the ring protruding from the bottom of the P2...

Page 8: ...should be closed low or zero resistance If the circuit is not closed return the P2621 NO2 VC to your supplier or CONSPEC for repair or replacement If the above resistance checks between terminals K1 a...

Page 9: ...A Current Source Control Outputs Optional Strobe TB1 V Strobe P2065 J3 OUT 4 First Alarm Piezo TB1 V Piezo P2065 J3 OUT 3 Second Alarm NOTE The Control Outputs are open collector transistors limited t...

Reviews: