4.  Press Key “4" once to remove the prompt. The LCD will read “000" (Waiting for 

operator to key in function number to go to).  

5.  Press Key “2" once and Key “3" once. The LCD will read “011" ( function number 

11, Manual Calibration).  

6.  Press Key “4" twice to enter function 11.  The message “ZERO INPUT” will scroll 

across the 3 digit LCD.  

7.  Press Key “4" once  to remove the prompt.  

*The LCD of the P2621-NO2/VC  Monitor will display the 3 digit Analog to Digital 
NO2unt (ADC).
 The ADC has a possible range of 0 - 999 with typical values of 
“050" with ZERO AIR applied, “400 - 500" with 250ppm (Half-scale) NO2 GAS 
applied, or “800-999" with 500ppm (full scale) NO2 gas applied.  

8.  Inject ZERO-AIR into the sensor.  Wait approximately 2 minutes.  The ADC should 

read approximately “050" with ZERO AIR flowing through the sensor. Press Key 
“4" once to accept the ZERO GAS calibration. (If the reading on LCD is outside the 
range of  25 – 100, the monitor should be sent back to the factory for in-house 
calibration) 
   

The message “SCALED INPUT” will scroll across the LCD followed by the 
message “FULL SCALE INPUT”.
  

9.  Press the Key “CONFIG/4" once WHILE either message is scrolling depending on 

whether you are using Full (20ppm) or Scaled (10ppm) NO2 Cal-Gas.

  

*The LCD of the P2621-NO2/VC  Monitor will display the 3 digit Analog to Digital 
Count (ADC).
  

10.  Remove the ZERO AIR and inject the NO2 CAL-GAS into the sensor.  The ADC 

should climb as the sensor responds to the Cal-Gas (typically ~ 450 with 10ppm, or 
~ 850 with 20ppm, if the reading is differed by more than 50%, sent the monitor 
back to the factory for in-house calibration). Wait approximately 2 minutes for the 
ADC to stabilize.  

11.  Press Key “4" once to accept the SCALED GAS calibration.   

*The message “CONSPEC Ver#” will scroll across the LCD (Software Version 

Number).  

Summary of Contents for P2621-NO2/VC

Page 1: ...Conspec Controls Inc P2621 NO2 VC Nitrogen Dioxide Ventilation Fan Controller Operations Manual Conspec Controls Inc 1 800 487 8450...

Page 2: ...the relay coil is energized whenever the P2621 NO2 VC is in a non alarm condition and the normally open contact terminal connections K1 K2 is held closed When any fault occurs the Fan relay is de ene...

Page 3: ...ystem design and installation Zoned systems are easily created when several sets of fans need to be controlled independently 1 Be sure to turn OFF power to fan Control system and 24 VAC power supply b...

Page 4: ...t a regular interval Conspec stipulates a gas injection into the sensor and verify the response of the sensor for every THREE MONTHS of operation To perform an actual gas verification simply inject a...

Page 5: ...g three door retaining screws Open the door of the P2621 NO2 VC and locate the 20 header pin Connector marked J2 in the middle of the left edge of the P2065 Smart Monitor Card Plug the P2621 P program...

Page 6: ...sensor Press Key 4 once to accept the ZERO GAS calibration If the reading on LCD is outside the range of 25 100 the monitor should be sent back to the factory for in house calibration The message SCAL...

Page 7: ...ector on the P2065 Smart Monitor Card Clip the wire tie securing the cable to the lower left hand corner of the P2065 Smart Monitor Card and discard Grasp the ring protruding from the bottom of the P2...

Page 8: ...should be closed low or zero resistance If the circuit is not closed return the P2621 NO2 VC to your supplier or CONSPEC for repair or replacement If the above resistance checks between terminals K1 a...

Page 9: ...A Current Source Control Outputs Optional Strobe TB1 V Strobe P2065 J3 OUT 4 First Alarm Piezo TB1 V Piezo P2065 J3 OUT 3 Second Alarm NOTE The Control Outputs are open collector transistors limited t...

Reviews: