I) SYSTEM DESCRIPTION  

Conspec’s P2621-NO2/VC Nitrogen Dioxide (NO2) Monitor / Ventilation Controller is 
designed for use where ventilation fans are installed to prevent the accumulation of 
dangerous levels of Nitrogen Dioxide.  Nitrogen Dioxide is a toxic byproduct of 
combustion and is contained in the exhaust of internal combustion engines. The P2621-
NO2/VC utilizes a programmable micro-Controller combined with a high-quality electro-
chemical Nitrogen Dioxide sensor to measure the NO2 level from 0-20ppm.  The P2621-
NO2/VC displays the NO2 level on the built-in LCD display, and activates a fan relay to 
ventilate the area when elevated concentrations (1 ppm) of NO2 are detected.  The 
P2621-NO2/VC’s audible alarm sounds if the NO2 level remains at an elevated level (3 
ppm) for more than 15 minutes to signal nearby persons to leave the area.  The P2621-
NO2/VC continually self-tests the internal electronic circuitry and the sensor, and signals 
if a fault is detected.  Front-panel LED indicators are provided for “Power”, “Fan (ON)”, 
“Alarm”, and “Fail”.  The P2621-NO2/VC is factory tested and calibrated prior to 
shipment.  Field calibrations are possible with the optional P1879-NO2 Calibration Kit 
and P2621-H handheld programmer module.  The P2621-NO2/VC operate on 24VAC 
power and consumes less than .15W max.  

The P2621-NO2/VC’s “Fan” relay is operated in the failsafe mode where the relay coil 
is energized whenever the P2621-NO2/VC is in a non-alarm condition and the normally-
open contact (terminal connections K1 & K2) is held closed.  When any fault occurs the 
“Fan” relay is de-energized and the normally-open contact (terminal connections K1 & 
K2) falls open.  The “Fan” relay is de-energized at start-up, when the NO2 level rises 
above 1ppm, when the internal diagnostics program detects a fault or when AC power to 
the unit is lost.  The “Fan” relay is re-energized when the fault is cleared. The P2621-
NO2/VC’s programming holds the “Fan” relay de-energized for a minimum of three 
minutes once activated to prevent short-cycling of the exhaust fans.    

The P2621-NO2/VC’s optional “Alarm” relay (terminal connections K3 & K4) 
operates on the same principle as the internal audible alarm.  The audible alarm is 
activated only after the NO2 level has exceeded 3ppm for 15 minutes.  The audible alarm 
(and optional “Alarm” relay) deactivate when the NO2 level drops below 3ppm.  

II)  POWER REQUIREMENTS  

Warning: The use of the P2621-NO2/VC unit with higher or lower voltages can 
damage the unit and cause improper operation or a hazardous condition.

  

The P2621-NO2/VC was engineered to be used with 24VAC power supply and a 24 
VAC relay control circuit.  The relay contacts are rated 5A@ 24VAC for use with an 
inductive load.  If the installation requires a higher voltage or greater load capacity, 
replace the relay unit with an appropriately rated relay (or use a second relay between the 
control relay and the load).  Power requirements for each P2621-NO2/VC are 24 VAC at 
0.5 amps.   

Summary of Contents for P2621-NO2/VC

Page 1: ...Conspec Controls Inc P2621 NO2 VC Nitrogen Dioxide Ventilation Fan Controller Operations Manual Conspec Controls Inc 1 800 487 8450...

Page 2: ...the relay coil is energized whenever the P2621 NO2 VC is in a non alarm condition and the normally open contact terminal connections K1 K2 is held closed When any fault occurs the Fan relay is de ene...

Page 3: ...ystem design and installation Zoned systems are easily created when several sets of fans need to be controlled independently 1 Be sure to turn OFF power to fan Control system and 24 VAC power supply b...

Page 4: ...t a regular interval Conspec stipulates a gas injection into the sensor and verify the response of the sensor for every THREE MONTHS of operation To perform an actual gas verification simply inject a...

Page 5: ...g three door retaining screws Open the door of the P2621 NO2 VC and locate the 20 header pin Connector marked J2 in the middle of the left edge of the P2065 Smart Monitor Card Plug the P2621 P program...

Page 6: ...sensor Press Key 4 once to accept the ZERO GAS calibration If the reading on LCD is outside the range of 25 100 the monitor should be sent back to the factory for in house calibration The message SCAL...

Page 7: ...ector on the P2065 Smart Monitor Card Clip the wire tie securing the cable to the lower left hand corner of the P2065 Smart Monitor Card and discard Grasp the ring protruding from the bottom of the P2...

Page 8: ...should be closed low or zero resistance If the circuit is not closed return the P2621 NO2 VC to your supplier or CONSPEC for repair or replacement If the above resistance checks between terminals K1 a...

Page 9: ...A Current Source Control Outputs Optional Strobe TB1 V Strobe P2065 J3 OUT 4 First Alarm Piezo TB1 V Piezo P2065 J3 OUT 3 Second Alarm NOTE The Control Outputs are open collector transistors limited t...

Reviews: