Installation Instructions
Expansion Module and Expansion Element
Program 0815
MV0815-0005a-EN
www.conductix.com translated document
page 4 of 26
3
Technical Specifications
Number of poles
4-, 6-, and 8-pole
Length of expansion
module
max. 1250 mm
PE position
In fourth place after L1, L2, and L3 (counting from the top)
PE system
PE
plus
error prevention
Conductor cross-
section
Rail 25 mm², expansion point 6 mm² with conductor loop
Current load
max. 54 A
Cable type
Double-insulated line (UL)
DANGER!
Danger of overloading!
Feeds must be designed and provided in such a way that the maximum current load
for the expansion module of 54 A is not exceeded.