Installation Instructions
Expansion Module and Expansion Element
Program 0815
MV0815-0005a-EN
www.conductix.com translated document
page 11 of 26
DANGER!
Risk of death by electrocution!
Contact with components carrying electrical power can lead to death by electrocution
or severe injury. Danger of injury due to shock reactions, falling, or being thrown
across the room due to electrical shock.
The main power supply (from the building) must be disconnected in the installation
area and secured against switching on again
Disconnect all electricity-supply infeeds
Check whether a voltage is still present in the components and take measures
where necessary
Install the conductor rail out of manual reach
Attach a sign saying "Risk of death by electrocution" with the relevant hazard sym-
bol in all areas with live components
The customer must ground metallic components
The customer must provide protective devices
Make sure there is sufficient stability in the area
WARNING!
The system must be designed and operated in accordance with the prevailing
ambient conditions!
WARNING!
Secure conductor rails against falling
In application areas with personnel traffic and at an installation height of 3 m or
more, conductor rails must be secured against falling!
ATTENTION!
To the side of the conductor rail there must, a clearance of at least 4 mm from
metal components must be maintained (see Fig. 7) to prevent mechanical col-
lisions and guarantee sufficient electrical insulation distances!
Fig. 7: Side clearance of at least 4 mm