Installation Instructions
Expansion Module and Expansion Element
Program 0815
MV0815-0005a-EN
www.conductix.com translated document
page 23 of 26
7
Adjusting the Gap Dimension
7.1
Expansion Module
Fig. 39: Preadjusting the gap on the expansion module
Fig. 40: Adjustment aid
The expansion gap is adjusted on the expansion modules during installation of the system. A plastic adjustment aid is
installed and clipped between the end caps to prevent loss (see Fig. 40). After installation of the entire system, the
adjustment aids on each expansion module installed must be removed during final inspection. This permits the expan-
sion of the different components.
The adjustment at the factory later permits a possible expansion of +/- 8 mm per expansion module at each individual
pole of the conductor rail.
ATTENTION!
The expansion modules can be adjusted with the separately available adjustment aid
for an installation temperature range b10° and +25° C. After installation is
complete, the adjustment aids must absolutely be removed.
If the installation temperature is significantly different, the individual expansion ele-
ments must be adjusted as described in chapter 7.2.
NOTICE!
The adjustment aids are separately available as an adjustment aid set
(material no.: 08-Z009-0014P).