Power Requirements
WARNING:
To reduce the risk of personal injury, fire, or damage to the
equipment, do not overload the AC supply branch circuit that provides power to
the system. Consult the electrical authority having jurisdiction over your facility’s
wiring and installation requirements for more information.
■
The power load needs to be balanced between available AC supply branch
circuits.
■
The overall system AC current load must not exceed 80 percent of the
branch circuit AC current rating.
■
If power strips are used, the load should not exceed 80 percent of the
power strip’s marked electrical current rating.
The installation of this equipment shall be in accordance with local/regional
electrical regulations governing the installation of Information Technology
Equipment by licensed electricians. This equipment is designed to operate in
installations covered by the National Electric Code (ANSI/NFPA 70, 1993)
and the code for Protection of Electronic Computer/Data Processing
Equipment (NFPA-75, 1992).
For electrical power ratings on options, refer to the rating label on the product
or to the user documentation supplied with that option.
Grounding
For proper operation and safety, this equipment is required to be properly
grounded in accordance with NFPA 70-1993, Article 250. All power
distribution devices, branch wiring, and receptacles must be listed
grounding-type devices.
When using power strips for electrical distribution, ensure that ground
integrity is maintained for each connection made. Plug each component into a
reliably grounded outlet.