IGS-NT Installation Guide
133
AVRi trim =
1/16 from minimum ( =6,25% => max. = 2,5V)
.
Volt/PF ctrl
:
AVR DCout bias
= 50%
VoltRegChar
= POSITIVE
The Vext input (connector CN1
– terminals 10 and 11) permits analogical remote control of output
voltage with a programmable variation range of up to ±10% (parameter 16, by default the setting is
±5%) with respect to the value set. If you want to use continuous voltage, it will be effective if it is in
the range between 0V and +2,5V. The input tolerates voltages from
–5V to +5V, but for values
exceeding the limits of 0V / +2,5V (or in the event of disconnection) it is automatically disabled and
the voltage adjustment goes back to the value set through the trimmer (if enabled) or through
parameter 19 (as shown on the picture).
Changing of DSR parameters requires PC with dedicated software and DI1-DSR unit!
DSR automatically detects presence of transformer for parallel operation (if used it works with
droop, if not used it works isochronous).
MECC ALTE DER1
AVRi+
AVRi-
18VAC
From
generator
OUT1
A
V
R
i
230/400VAC
0VAC
AVRI COM
AVRI OUT
IG- AVRi
TRANS
IG
-
COM
29
30
AVRi trim =
1/16 from
minimum
Volt/PF ctrl
:
AVR DCout bias
= 50%
VoltRegChar
= POSITIVE
Alternative connection for
DER1
AVRi+
AVRi-
18VAC
From
generator
OUT1
A
V
R
i
230/400VAC
0VAC
AVRI COM
AVRI OUT
IG- AVRi
TRANS
IG
-
OUT2
30
32
AVRi trim =
maximum
Volt/PF ctrl
:
AVR DCout bias
= 50%
VoltRegChar
= POSITIVE
Remove jumpers connecting input 27 to 28 and input 31 to 32.